Auxiliary Area Allocations
A751
A752
A800
A802
A809
A810
A811
Word
11
12
13
14
15
00 to 15 DM Save Password
00 to 15 Analog Input PV
00
07
08
09
15
00 to 15 Number of Analog Samples
00 to 15 Analog Output 1 Output Value
00 to 15 Analog Output 2 Output Value
Bits
Saved DM Data Invalid Flag
Invalid DM Save Password Flag
DM Backup Error Flag
Saving DM Flag
DM Save Start Bit
Analog Input Status
Name
ON if the DM data in flash memory was invalid when it was read.
This flag is cleared when DM data is saved.
ON if A752 contains the wrong password.
ON if the DM data save operation failed.
ON when DM data is being saved to flash memory.
Write the password to A752 and turn this bit ON to save DM data to
flash memory. The data can be saved only when the Motion Control
Module is in PROGRAM mode.
Write A5A5 hex to this word and turn ON the DM Save Start Bit
(A751.15) to transfer DM data to flash memory (PROGRAM mode
only). When the DM data transfer is completed, this word is automat-
ically cleared.
Contains the value input from the analog input port (using either the
END refresh or immediate refresh) in 4-digit hexadecimal.
The PV range depends on the input range:
• 0 to 10 V:
• 0 to 5 V or 1 to 5 V:
• 10 to 10 V:
User Adjustment
Completed
Analog Sampling
Started
Factory Adjustment
Data Error
User Adjustment
Data Error
Analog Sampling
Overlap
Indicates the number of data samples actually input since sampling
started.
When an END refresh is selected, the 4-digit hexadecimal value set
here by the user is output from analog output port 1.
When immediate refreshing is selected, the 4-digit hexadecimal
value being output from analog output port 1 is stored here for moni-
toring. The output value range depends on the output range, as
shown below.
• 0 to 10 V, 0 to 5 V or 1 to 5 V: FF38 to 1068 hex
• 10 to 10 V: EA84 to 157C hex
Note
1. Set the analog output method (END or immediate refreshing) with
2. Specify the output range with the output 1 setting.
This word has the same settings as the analog output 1 output value
(A560), above. (When an END refresh is selected, set the value to
output from analog output port 2. When an immediate refresh is
selected, the output value is stored here for monitoring.)
Note
1. Set the analog output method (END or immediate refresh) with the
2. Specify the output range with the output 2 setting.
the System Setup’s output method setting. A setting of 0 hex spec-
ifies an END refresh. This setting applies to both analog output 1
and 2.
System Setup’s output method setting. A setting of 0 hex specifies
an END refresh. This setting applies to both analog output 1 and 2.
OFF: Not adjusted
ON: Adjustment completed
OFF: Not started
ON: Started
OFF: No Error
ON: Error (Checked at power ON.)
OFF: No Error
ON: Error (Checked at power ON.)
OFF: Normal sampling
ON: The next sampling operation occurred
before the present sampling operation com-
pleted.
FE70 to 20D0 hex
FF38 to 1068 hex
DDA0 to 2260 hex
Function