Module Wiring
Grounding
94
• GR is the ground terminal. To help prevent electric shock, ground this ter-
• LG is a noise-filtered neutral terminal. If noise is a significant source of
• If connecting the line ground and ground terminals, always ground both to
• The ground wire should not be more than 20 m long.
• The FQM1 is designed to be mounted so that it is isolated (separated)
• Do not share the FQM1's ground with other equipment or ground the
PA205R
minal to less than 100
sectional area of 2 mm
errors and to prevent electrical shocks, connect the line ground terminal
to the ground terminal and ground both with a ground resistance of less
than 100
less than 100
from the mounting surface to protect it from the effects of noise in the
installation environment (e.g., the control panel).
FQM1 to the metal structure of a building. Doing so may worsen opera-
tion.
POWER
AC100-240V
Control panel
OUTPUT
AC240V
DC24V
INPUT
or less.
RUN
FQM1
ground terminal
L2/N
L1
to prevent electrical shock.
Ground the FQM1 system
separately to a resistance
of 100
2
).
or less.
and use special ground wire (minimum cross-
LG (Noise-filtered neutral terminal)
Ground separately with a resistance of
less than 100
noise and to prevent electric shocks.
GR (Ground)
Ground this terminal separately to less
than 100
to prevent electric shock.
to increase resistance to
Section 3-2