Error Processing
9-2-9
9-2-10 System Setup Error Check
310
Cycle Time Overrun Error
watch cycle time set in the
cycle time less than the
Cycle Time Overrun Error Check
Is the assumed
System Setup?
Are interrupts
being used?
System Setup Error occurred
occurred
the System Setup Error
No
Location (A406)?
Yes
What is in
Other value
Yes
No
Interrupt Processing Time
#0146 hex (326), #0148 hex (328), or
maximum ring counter value
setting OK?
Is the Max.
Yes
No
The program execution time exceeded the
watch cycle time. Increase the watch cycle
time setting in the System Setup.
It is possible that the error occurred
because the interrupt task execution time
was too long.
It is possible that the error occurred
because two or more interrupt tasks were
executed. Check how often interrupt tasks
are executed.
There may be an error in the program.
Check all tasks, particularly instructions that
control loops ,such as the JMP instruction.
Set the proecessing mode correctly.
A communications error may have occurred
during the transfer from the CX-Programmer.
Transfer the System Setup again.
Section 9-2
Not cause
of error