Each Special I/O Unit is allocated 10 words based on its unit number, as shown in the following table.
Words in the Special I/O Unit Area that are not allocated to Special I/O Units can be used only in the program
as work words. Bits in the Special I/O Unit Area can be force-set and force-reset.
The contents of the Special I/O Unit Area will be cleared in the following cases:
1. The operating mode is changed from PROGRAM to RUN or MONITOR mode or vice-versa.
2. The FQM1’s power supply is turned OFF and ON again.
3. The Special I/O Unit Area is cleared from the CX-Programmer.
4. PLC operation is stopped when a fatal error other than an FALS(007) error occurs. (The contents of the Spe-
B-7
The Serial PLC Link Area contains 90 words with addresses ranging from CIO 3100 to CIO 3189. Words in the
Serial PLC Link Area can be used for data links with other PLCs.
Serial PLC Links exchange data among CPU Units and Coordinator Modules via the built-in RS-232C ports,
with no need for special programming.
The Serial PLC Link allocation is set automatically by means of the following PLC Setup settings at the Polling
Unit.
374
I/O Memory
CIO 2000 to CIO 2009
CIO 2010 to CIO 2019
CIO 2020 to CIO 2029
CIO 2030 to CIO 2039
CIO 2040 to CIO 2049
CIO 2050 to CIO 2059
CIO 2060 to CIO 2069
CIO 2070 to CIO 2079
CIO 2080 to CIO 2089
CIO 2090 to CIO 2099
CIO 2100 to CIO 2109
CIO 2110 to CIO 2119
CIO 2120 to CIO 2129
CIO 2130 to CIO 2139
CIO 2140 to CIO 2149
CIO 2150 to CIO 2159
CIO 2160 to CIO 2169
CIO 2170 to CIO 2179
CIO 2950 to CIO 2959
Allocated words
cial I/O Unit Area will be retained when FALS(007) is executed.)
• Serial PLC Link Mode
• Number of Serial PLC Link transfer words
• Maximum Serial PLC Link unit number
Serial PLC Link Area
Do not use unit numbers
0 to 9 in the FQM1.
These words (CIO 2000
to CIO 2099) can be used
as work words.
10
11
12
13
14
15
16
17
95
Unit number
Appendix B