CPU Standby
Fatal Errors
Error Processing
Stopped
Operating
status
CPU
standby
name
Error
None
in Auxiliary
Error flags
Note
Area
If the following LED indicator condition appears when the power is turned ON,
it indicates that the FQM1 is in CPU standby status.
When the FQM1 is turned ON, cyclic servicing starts after the Coordinator
Module recognizes all of the connected Motion Control Modules and CJ-
series Units. Operation can be started at that point.
If the startup mode is RUN or MONITOR mode, the FQM1 will remain in
standby status until all of the Motion Control Modules have been recognized.
The FQM1 will go into CPU standby when a Too many I/O points error, unit
number error, duplicated number error, or I/O setting error is detected when
the power is turned ON. The ERR Indicator will be lit in this case. Eliminate
the cause of the error and turn the power ON again.
When a CJ1W-SPU01 SPU Unit is mounted, it takes the Coordinator Module
about 20 seconds to recognize the SPU Unit, so the CPU standby time will be
longer then usual.
If the following LED indicator condition appears during operation (in RUN or
MONITOR mode), it indicates that a fatal error has occurred.
The fatal error’s error contents will be displayed in the Error Tab in the CX-Pro-
grammer’s Error Window. Determine the cause of the error from the error
message and related Auxiliary Area flags/words and correct the cause of the
error.
Errors are listed in order of importance. When two or more errors occur at the
same time, the more serious error’s error code will be recorded in A400.
The I/O memory will be cleared when a fatal error other than FALS occurs.
(The I/O memory will not be cleared when FALS is executed to generate a
fatal error.)
Module Indicators
Unit Indicators
None
Error code
Power Supply
Power Supply
(in A400)
POWER
POWER
Lit
Lit
None
Error con-
tents
RDY
OFF
RDY
Lit
(Coordinator Module and Motion Control Modules)
A Motion Control Module or
CJ-series Unit did not start
up properly.
Probable cause
RUN
RUN
OFF
OFF
Module Indicators
Module Indicators
ERR
ERR
OFF
Lit
PRPHL
PRPHL
---
---
Replace the Motion Control
Module or CJ-series Unit.
COMM1
COMM1
Remedy
---
---
Section 9-2
COMM2
COMM2
---
---
303