Error Processing
9-2-5
CPU Errors
CPU Reset
302
Stopped
Stopped
Operating
Operating
status
status
Error Tables
CPU
error
CPU
reset
name
Error
name
Error
None
Error flags
iary Area
None
in Auxil-
in Auxiliary
Error flags
Note
Area
Note Always confirm the safety of connected equipment before turning the power
The following tables show the errors which can occur in the FQM1 and indi-
cate the probable cause of the errors.
supply OFF or ON.
If the following LED indicator condition appears during operation (in RUN or
MONITOR mode), it indicates that a CPU error has occurred. The CX-Pro-
grammer cannot be connected if a CPU error has occurred.
If a fatal error occurs, the RDY and ERR indicators will be lit and the RUN indi-
cator will be OFF, but a CX-Programmer can be connected. This difference
can be used to distinguish between a CPU error and other fatal errors.
The following indictor status shows that the CPU Unit has been reset (not a
CPU error). A Programming Device cannot be connected in this condition.
When the power supply to an Expansion Rack is interrupted, the Coordinator
Module will stop running and perform the same power interruption procedure
that is performed when the power supply is interrupted to the Coordinator
Module itself.
None
Error code
Module Indicators
Module Indicators
(in A400)
None
Error code
Power Supply
Power Supply
(in A400)
POWER
POWER
Lit
Lit
None
Error con-
None
Error con-
tents
tents
RDY
OFF
RDY
OFF
(Coordinator Module and Motion Control Modules)
(Coordinator Module and Motion Control Modules)
Power is not being supplied
to the Expansion Rack.
I/O Control Module is not
connected correctly, e.g.,
more than one is con-
nected or one is connected
to an Expansion Rack.
The I/O Connecting cable
is not connected correctly,
e.g., the connections to the
input and output connec-
tors on the I/O Interface
Unit are reversed.
A WDT (watchdog timer)
error occurred in a Module.
(This error does not nor-
mally occur)
Probable cause
Probable cause
RUN
RUN
OFF
OFF
Module Indicators
Module Indicators
ERR
ERR
OFF
Lit
PRPHL
PRPHL
Supply power to the Expan-
sion Rack.
Turn OFF the power supply,
correct the connections,
and turn the power supply
back ON.
Turn OFF the power supply,
correct the connections,
and turn the power supply
back ON.
---
---
Turn the power OFF and
restart. The Module may be
damaged. Contact your
OMRON representative.