Applicable Models
Overview
Note
The FQM1-MMA22 Motion Control Module can input analog input signals at
high-speed (A/D conversion time: 40 s).
One of five signal types for analog inputs can be selected: 10 to +10 V, 0 to
10 V, 0 to 5 V, 1 to 5 V, and 4 to 20 mA.
Analog input values are stored in the Motion Control Module’s Auxiliary Area
in A800. The stored input value is the analog input value read at END refresh-
ing. It is also possible to adjust the analog input values.
The PRV(881) instruction can also be used to read the latest analog input
value through immediate refreshing. Analog signals can be input from pres-
sure sensors, position meters, or sensors that require high-speed input pro-
cessing
Consequently, this function allows simple, low-cost pressure control, tension
control, or other control applications requiring high-speed mechanical mea-
surement (distortion/thickness/length).
The analog input responsiveness has been set relatively high to increase the
processing speed. The high responsiveness may result in input signal distor-
tion by external noise or interference. Take steps to suppress noise if the
Motion Control Module is being used in an environment with a lot of noise.
When the Motion Control Module’s analog input value is being used, addi-
tional noise countermeasures can be added to the program such as using
END refreshing and filtering the input values with AVG instructions.
Sensor
(pressure, displacement, etc.)
FQM1-MMA22
Model
such
Selected signal range:
0 to 5 V, 1 to 5 V, or
4 to 20 mA
10 to +10 V, 0 to 10 V,
as
Motion Control Module for Analog I/O
a
displacement
FQM1-MMA22
Motion Control Module
High speed input
(A/D conversion time:
40 s)
A
D
sensors/end-measuring
Functions
Immediate
refreshing
Stores the data
when instruction
is executed.
User program
I/O memory
Section 7-9
PRV
sensors.