Note
The terminals on the I/O Unit are M3, self-raising terminals with screws.
(1) Use crimp terminals for wiring.
(2) Do not connect bare stranded wires directly to terminals.
(3) Tighten the terminal block screws to the torque of 0.5 N·m.
(4) Use crimp terminals (M3) having the dimensions shown below.
• The current capacity of electric wire depends on factors such as the ambi-
• Verify that each Unit is mounted securely.
• Do not remove the protective label from the top of the Unit until wiring has
• Remove the label after wiring has been completed to allow air circulation
• Wire the Units so that they can be easily replaced.
• Make sure that the I/O indicators are not covered by the wiring.
• Do not place the wiring for I/O Units in the same duct or raceway as power
• Tighten the terminal screws to the torque of 0.5 N·m.
• The I/O Units are equipped with removable terminal blocks.
ent temperature and insulation thickness as well as the gauge of the con-
ductor.
been completed. This label prevents wire strands and other foreign matter
from entering the Unit during wiring procedures.
needed for cooling.
lines. Inductive noise can cause errors in operation.
6.2 mm max.
17.5 mm
During wiring
OD211
Screw (M3 screw with
self-raising pressure plate)
OD211
0 1 2 3 4 5 6 7
8 9 10 11 12 13 14 15
After wiring
6.2 mm max.
Remove the label.
Section 3-2