AC Power Source
Isolation Transformer
Power Supply Capacity
Terminal Screws and
Crimp Terminals
Module Wiring
!Caution Tighten AC power supply terminal block screws to a torque of 1.2 N·m. Loose
Note
Note
Note
The RUN output function is provided only for the CJ1W-PA205R Power Sup-
ply Unit. It is not provided on the CJ1W-PA202 Power Supply Unit.
The FQM1's internal noise isolation circuits are sufficient to control typical
noise in power supply lines, but noise between the FQM1 and ground can be
significantly reduced by connecting a 1-to-1 isolation transformer. Do not
ground the secondary coil of the transformer.
The power consumption will be 100 VA max. for the CJ1W-PA205R and 50 VA
for the CJ1W-PA202, but there will be a surge current of at least 5 times the
max. current when the power is turned ON.
The terminals on the Power Supply Unit use M4, self-raising terminal screws.
screws may cause shorts, malfunctions, or fire.
(1) Use crimp terminals for wiring.
(2) Do not connect bare stranded wires directly to terminals.
(3) Tighten the terminal block screws to a torque of 1.2 N·m.
(1) Supply power to all of the Power Supply Units from the same source.
(2) Do not remove the protective label from the top of the Power Supply Unit
(3) Do not forget to remove the label from the top of the Power Supply Unit
• Supply 100 to 240 V AC.
• Keep the voltage fluctuations within the specified range.
• If one power supply phase of the equipment is grounded, connect the
grounded phase side to the L2/N terminal.
100 to 240 V AC
Use M4 crimp terminals for AC power supplies.
until the wiring has been completed. This label prevents wire strands and
other foreign matter from entering the Unit during wiring procedures.
after wiring the Unit. The label will block air circulation needed for cooling.
Crimp Terminals for AC Power Supply
7 mm max.
Supply voltage
20 mm max.
85 to 264 V AC
Tightening torque 1.2 N m
Allowable voltage fluctuations
M4 self-raising terminal screws