Checking SFC Programs
48
A
B
Level
Subchart entry posi err
Subchart err
Subchart return posi err
Term different
Too many actions
Too many branches, joins
Too many initial steps
Too many steps
Too many transitions
Transition connect err
Transition # range err
Transition bit # range err
Undef. action
Undef. AQ
Undef. FV bit
Undef. intrpt prog #
Undef. step
Undef. subchart entry step
Undef. transition
Undef. transition bit
Branch–join
Connect err
Initial step loc. error
Intrpt entry posi err
Multi intrpt entry terms
Multi subchart entries
No initial step
SFC jump posi err
Error Message
The subchart entry terminal and subchart
entry step are not used as a pair or are not
in the correct positions.
Only a single step has been created in a
subchart program.
The subchart return terminal and subchart
return step are not used as a pair or are
not in the correct positions.
Subchart or interrupt return terminal does
not exist, or a different type of return
terminal has been used.
More than 1,500 actions have been used
in a single sheet.
There is a branch to or a join from more
than 15 steps.
More than 31 initial steps have been used
in a single sheet.
More than 100 steps have been used in a
single sheet.
More than 100 transitions have been used
in a single sheet.
The transition is not connected correctly.
The transition number is too large.
The transition bit address is too large.
No action number.
No AQ.
No bit address for the FV I/O name.
No interrupt program number (for
scheduled or I/O interrupts).
No step number.
No subchart entry step number.
No transition number.
No transition bit address.
Conditional or parallel branches and joins
were not used in pairs or one of the SFC
parts was omitted.
The connection lines are connected
incorrectly.
An initial step was used in a subchart or
interrupt program.
The interrupt entry terminal and interrupt
entry step are not used as a pair.
More than one interrupt entry terminal was
used.
More than one subchart entry terminal was
used.
An initial step does not exist.
Previous SFC part was omitted.
Description
Check and correct the program.
Check the PC model and correct
the program.
Enter an action number.
Enter an AQ.
Enter a FV bit address.
Enter an interrupt program
number.
Enter a step number.
Enter a subchart entry step
number.
Enter a transition number.
Enter a transition bit address.
Check and correct the program.
Remedy
Section 2-9