PC Setup
Letter
M
K
N
P
Q
R
L
First words for local racks
(1st Rack addr)
First words for group-1 and
group-2 Slaves
(Group 1,2 1st addr)
First words for I/O Terminals
(Trans I/O addr)
First words for group-3 Slaves
(Group 3 RT 1st addr)
Momentary power interruption
time (Power break)
Cycle time
Cycle time monitoring time
(Watch cycle time)
Name
Designate the first word for each CPU, Expansion CPU, and Expansion I/O
Rack. The first word can be set between 0 and 511. Do not allow word
allocations to overlap. Recreate the I/O table after changing this setting.
(Default: 0 for CPU Rack, no designation for other Racks (continue on from
previous Racks))
Designate the first words for each Master for SYSMAC BUS/2 group-1 and
group-2 Slaves to between CIO 0000 and CIO 0999. Recreate the I/O table
after changing this setting.
(Default: Group 1: 50 words per Master starting at intervals of 200 words
with the first interval starting from CIO 200. Group 2: 50 words per Master
starting at intervals of 200 words with the first interval starting from CIO
250.)
Designate the first word for each Master for SYSMAC BUS I/O Terminals
between CIO 0000 and CIO 2555. Allocations will not be changed unless the
first word allocated to the Master is changed. Recreate the I/O table after
changing this setting.
Do not allow words allocated to these I/O Terminals to overlap with the bits
set as holding bits. Outputs that are ON at the end of operation will remain
ON when operation is stopped if I/O Terminals are allocated words also
specified as holding bits.
(Default: 32 words per I/O Terminal starting from CIO 2300)
Designate the first word for each SYSMAC BUS/2 group-3 Slave between
CIO 0000 and CIO 0999 and for each SYSMAC BUS Slave Rack between
CIO 0000 and CIO 2555. Recreate the I/O table after changing this setting.
Do not allow words allocated to Slave to overlap with the bits set as holding
bits. Outputs that are ON at the end of operation will remain ON when
operation is stopped if Slaves are allocated words also specified as holding
bits.
(Default: Normal allocation using consecutive words)
Designate the momentary power interruption time between 0 and 10 ms.
Operation will continue for momentary power interruptions if the power
supply is restored within this time after a power interruption.
If the momentary power interruption time is set to greater than 0 ms,
Peripheral Device communications may be disrupted and may go on
standby for momentary power interruptions.
This setting will be ignored and the default value will be used if a C500
Expansion I/O Rack is connected to the System.
This setting is effective immediately.
(Default: 0 ms)
Set the minimum cycle time to between 0 and 32,000 ms. If the actual cycle
time is less than the set cycle time, execution will be halted until the set
cycle time elapses before the next scan is executed. If the actual cycle time
exceeds the set cycle time, the setting is ignored and the next cycle is
executed when the current cycle is complete. This setting is effective
immediately.
In the actual operation of the PC, there may be a deviation of 3 to 4 ms. If a
break-in program is being executed, a further deviation due to the execution
of the break-in program will be involved.
(Default: Variable cycle)
Designate the maximum cycle time between 10 and 40,000 ms. If the cycle
time exceeds this value, a fatal error will occur and A40108 will be turned
ON (Cycle Time Too Long Flag). This setting is effective immediately.
(Default: 1,000 ms)
Operation
Section 7-2
227