Specifications of C500CP131

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
PC Setup
224
PC Setup Details
Letter
Letter
N
P
Q
R
S
A
B
C
T
First words for Slaves Racks
(SYSMAC BUS/2 and SYSMAC
BUS)
(Group 3 RT 1st addr)
Momentary power interruption time
(Power break)
Cycle time
Cycle time monitoring time
(Watch cycle time)
Error log area
Display modes at startup
(IORF, RT display)
Hold
areas
Startup
hold
Startup mode
Hold area
Hold Racks
(Hold bits)
Forced Status Hold
Bit status (A00013)
(Forced status)
IOM Hold Bit status
(A00012)
(I/O bits)
Restart
Continuation Bit
status (A00011)
(Power on flag)
Name
Name
The status of bits specified here will be maintained when power is turned off
and on.
The holding bits can be set in any continuous range between CIO 1000 to
CIO 2399.
(Default: CIO 1200 to CIO 1499)
The output status on Racks specified here or in all Slaves connected to
Masters specified here will be maintained when operation is stopped or
when PC operating modes are changed. Status will not be maintained for
these outputs when power is turned off. Regenerate the I/O table or turn PC
power off and on after changing this parameter.
(Default: nothing held)
Specify whether the status of the Forced Status Hold Bit is to be maintained
or reset to OFF when power is turned on. This setting is effective the next
time the power is turned ON.
(Default: A00013 turned OFF)
Specify whether the status of the IOM Hold Bit is to be maintained or reset to
OFF when power is turned on. This setting is effective the next time the
power is turned ON.
(Default: A00012 turned OFF)
Specify whether the status of the Restart Continuation Bit is to be
maintained or reset to OFF when power is turned on. This setting is effective
the next time the power is turned ON.
(Default: A00011 turned OFF)
The following settings are required to continue operation after a power
interruption:
IOM Hold Bit (A00012):
Forced Status Hold Bit (A00013): ON and maintained
IOM Hold Bit status:
Restart Continuation Bit status:
Startup mode:
Power OFF interrupt:
Designate the PC operating mode to be set when PC power is turned ON.
This setting is valid the next time the power is turned ON.
(Default: PROGRAM)
To set the first word for each Slave
Rack.
To set the length of time to be
treated as a momentary power
interruption.
To set a minimum cycle time.
To set a maximum cycle time.
To set the number of records
recorded and the words in which
they are recorded.
To set the startup display mode for the 7-segment displays on I/O Control
Units, I/O Interface Units, and SYSMAC BUS/2 Slave Racks.
Function
Operation
ON and maintained
Hold
Hold
RUN
Exists
To simplify word allocations, to
prevent changes in allocations, or
to allow for expansion without
changes in allocations.
To enable ignoring short primary
voltage drops for poor power
supplies.
To eliminate irregular I/O delays.
To stop operation when a specified
cycle time is exceeded or to enable
longer cycle times by setting a high
maximum.
To increase the number or error
records that are maintained.
Normal application(s)
Section 7-2