There are four separate controls that can be set, as shown below. The current
settings are displayed on the far right. To change a setting, select the item and
select the desired treatment.
Detect low batt: Set to Yes to treat detection of a low CPU battery as an error.
Err on power off: Set to Yes to treat detection of a momentary power interrup-
tion as an error.
CPU standby: Set to Yes if you want the CPU to go on standby during system
initialization.
Measure CPU SIOU cycle: Set to Yes if you want the CPU Bus Unit servicing
cycle to be measured and stored in memory (A310 to A325).
There are eight separate controls that can be set, as shown below. The current
settings are displayed on the far right. To change a setting, select the item and
select the desired treatment.
Execute process: Specify whether Peripheral Device servicing is to be ex-
ecuted synchronously or asynchronously with program execution.
I/O interrupt: Specify whether or not I/O interrupts are to be interrupted to ex-
ecuted higher-priority I/O interrupts.
Power off interrupt: Specify whether of not the power off interrupt is to be
executed.
Dup action process: Specify whether or not an error is to be generated if the
same action is executed simultaneously from two locations in the SFC program.
Step timer: Specify the unit for the step timer.
Startup trace: Specify whether or not a trace is to be automatically executed
when PC power is turned on.
*DM BIN/BCD: Specify if indirect addresses are to be treated as binary or BCD.
Multiple Use of JMP000: Enables or disables usage of multiple JMP000
instructions.