Checking SFC Programs
A
Level
AQ error
AQ hold option err
Branch-join
Connect err
Dup output bit
Dup step #
Dup transition #
Duplicate action program (1
step)
FV bit range err
Initial step loc. err
Intrpt entry posi error
Intrpt prog err
Intrpt program # err
Intrpt return posi err
No subchart entry
No subchart return
No intrpt return term
No intrpt entry term
No SFC jmp dest
No SFC jmp entry
Sel branch error
Sel join error
SFC jump posi err
Simul branch err
Simul join err
Step connect err
Step # range err
Subchart dummy step error
Error Message
The SV is out of range or not set for one of
the following AQs: D, DH, L, LH, SD, DS,
SL.
The H (hold) qualifier was used with an AQ
other than N, P, R, D, or L.
Two branch lines have been connected
vertically.
The connecting lines are not positioned
correctly.
The same bit address has been used more
than once in a single step.
The same step number has been used
more than once in a single sheet.
The same transition number has been
used more than once in a single sheet.
The same action number has been used
more than once in a single step.
The FV value is out of range.
An initial step has been used as the entry
step or return step for a subchart or
interrupt.
The interrupt entry terminal and interrupt
entry step are not used as a pair or are not
in the correct positions.
Only a single step or transition has been
created in an interrupt program.
The interrupt program number is out of
range (for scheduled or I/O interrupts).
The interrupt return terminal and interrupt
return transition are not used as a pair or
are not in the correct positions.
No subchart entry terminal exists.
No subchart return terminal exists.
The interrupt return terminal does not exist. Enter an interrupt return terminal.
Interrupt entry terminal does not exist.
No jump destination step number.
No jump destination.
Conditional branch used from multiple
steps.
Conditional join used to multiple steps.
The jump is connected to a branch.
Multiple transitions have been used for a
parallel branch.
Multiple transitions have been used for a
parallel join.
Steps not connected correctly.
The step number is too large.
A subchart dummy step has been used as
a subchart/interrupt entry step or return
step.
Description
Check and correct the program.
Enter a subchart entry terminal.
Enter a subchart return terminal.
Enter an interrupt entry terminal.
Enter a jump entry step number.
Check and correct the program.
Check the PC model and correct
the program.
Check and correct the program.
Remedy
Section 2-9