CS1D-DPL02D Omron, CS1D-DPL02D Datasheet - Page 563

no-image

CS1D-DPL02D

Manufacturer Part Number
CS1D-DPL02D
Description
CS1D Dual IO Exp
Manufacturer
Omron
Datasheet

Specifications of CS1D-DPL02D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
528
Auxiliary Area Allocations
A401
Words
Address
A40111
A40112
A40113
A40114
A40115
Bits
Too Many
I/O Points
Flag
(Fatal
error)
Fatal Inner
Board
Error Flag
(Error
causing
switch to
simplex
operation)
(Single
CPU Sys-
tems or
Process-
control
CPU Unit)
Duplica-
tion Error
Flag
(Fatal
error)
I/O Bus
Error Flag
(Fatal
error)
Memory
Error Flag
(Fatal
error)
Name
ON when the number of I/O points
being used in Basic I/O Units
exceeds the maximum allowed for
the PLC.
CPU Unit operation will stop and the
ERR/ALM indicator on the front of
the CPU Unit will light.
This flag will be turned OFF when
the error is cleared.
ON when there is an Inner Board
Error (Watchdog timer error). The
ERR/ALM indicator will light.
With a Single CPU System, CPU
Unit operation will stop. With a
Duplex CPU System in Duplex
Mode, operation will switch to the
standby CPU Unit and operation will
continue. With a Duplex CPU Sys-
tem in Simplex Mode, CPU Unit
operation will stop.
This flag will be turned OFF when
the error is cleared, but will be
turned ON again unless the cause of
the error is eliminated.
ON in the following cases:
Two CPU Bus Units have been
assigned the same unit number.
Two Special I/O Units have been
assigned the same unit number.
Two Basic I/O Units have been allo-
cated the same data area words.
CPU Unit operation will stop and the
ERR/ALM indicator on the front of
the CPU Unit will light.
The duplicated unit number is indi-
cated in A409 to A416.
(This flag will be turned OFF when
the error is cleared.)
ON when an error occurs in a data
transfer between the CPU Unit and a
Unit mounted to a slot.
CPU Unit operation will stop and the
ERR/ALM indicator on the front of
the CPU Unit will light.
The slot number (00 to 08) where
the I/O Bus Error occurred is written
to A40400 to A40407 in binary and
the rack number (00 to 07) is written
to A40408 to A40415 in binary
(This flag will be turned OFF when
the error is cleared.)
ON when an error occurred in mem-
ory or there was an error in auto-
matic transfer from the Memory
Card when the power was turned
ON. The ERR/ALM indicator on the
front of the CPU Unit will light.
With a Single CPU System, CPU
Unit operation will stop. With a
Duplex CPU System in Duplex
Mode, operation will switch to the
standby CPU Unit and operation will
continue. With a Duplex CPU Sys-
tem in Simplex Mode, CPU Unit
operation will stop.
The location where the error
occurred is indicated in A40300 to
A40308, and A40309 will be turned
ON if there was an error during auto-
matic transfer at start-up.
This flag will be turned OFF when
the error is cleared. (The automatic
transfer at start-up error cannot be
cleared without turning off the PLC.)
Function
ON: Error
OFF: No error
ON: Error
OFF: No error
ON: Duplication
error
OFF: No dupli-
cation
ON: Error
OFF: No error
ON: Error
OFF: No error
Settings
Cleared
Cleared
Cleared
Cleared
Cleared
change
Status
mode
after
Cleared
Cleared
Cleared
Cleared
Cleared
Status at
startup
---
---
---
---
---
Timing
Appendix B
A407
A242
A410 to
A416
A404
A40300
to
A40308,
A40309
settings
Related
flags,

Related parts for CS1D-DPL02D