CS1D-DPL02D Omron, CS1D-DPL02D Datasheet - Page 438

no-image

CS1D-DPL02D

Manufacturer Part Number
CS1D-DPL02D
Description
CS1D Dual IO Exp
Manufacturer
Omron
Datasheet

Specifications of CS1D-DPL02D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Non-fatal Errors
Duplex Errors
(Errors Causing a Switch
to Simplex Operation for
Duplex CPU Systems)
Troubleshooting Table
Error Processing
Duplex
verifica-
tion error
Duplex
bus error
Error
DPL VER-
IFY ERR
DPL BUS
ERR
Program-
Console
display
ming
indicator
Flashing
red
Lit red
STATUS
DPL
iary Area
A31600,
A40214
A31601,
A40214
flags in
Auxil-
Error
Operation will continue for any of the following errors for a Duplex CPU Sys-
tem in Duplex Mode or in Simplex Mode, or for a Single CPU System. For
some of these errors, operation for a Duplex CPU System will switch from
Duplex Mode to Simplex Mode and for other errors, operation will remain in
Duplex Mode. These are listed separately below.
Connect the CX-Programmer or a Programming Console to display the error
message (in the PLC Error Window on the CX-Programmer). The cause of
the error can be determined from the error message and related Auxiliary
Area flags and words.
For a Duplex CPU System, duplex errors will cause operation to be switched
to Simplex Mode, but operation will continue in RUN or MONITOR mode.
A non-fatal duplex error has occurred if the indicators have the following con-
ditions during operation in RUN or MONITOR mode.
Duplex errors are unique to Duplex CPU Systems and will not occur on Single
CPU Systems.
For all of the following errors, operation will continue if the error occurs in
Duplex Mode or in Simplex Mode. If it occurs in Duplex Mode, operation will
switch to Simplex Mode.
Power Supply Unit
CPU Unit
Duplex Unit (with
error occurring on
active CPU Unit)
0011
0010
code (in
A400)
Error
A317
---
Flags
word
data
and
POWER
RUN
ERR/ALM
INH
PRPHL
COMM
DPL STATUS
Active CPU Unit
indicators
Standby CPU Unit
indicators
One of the following is not
the same between the two
CPU Units.
• CPU Unit model number
• Parameter area data
• User program
• Inner Board internal data
An error occurred on the
duplex bus in the Duplex
System.
inconsistency
Probable cause
ACTIVE
CPU STATUS
ACTIVE
CPU STATUS
Check the items to the left between
the two CPU Units and be sure they
are the same and then toggle the
power supply.
If the problem persists, retransfer the
user program and parameter area
data (including the PLC Setup CPU
Bus Unit settings and I/O tables) to the
active CPU Unit.
If the problem persists, replace the
Duplex Unit.
Prepare the system to stop operation
and then press the initialization button
on the Duplex Unit.
If the problem persists, replace the
Duplex Unit.
Possible remedy
Lit green
Lit green
Flashing red
---
---
---
Duplex verification
error: Flashing red
Duplex bus error:
Lit red
Lit green
Lit green
Not lit
Lit green
Section 10-2
403