CS1D-DPL02D Omron, CS1D-DPL02D Datasheet - Page 139

no-image

CS1D-DPL02D

Manufacturer Part Number
CS1D-DPL02D
Description
CS1D Dual IO Exp
Manufacturer
Omron
Datasheet

Specifications of CS1D-DPL02D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Unit Current Consumption
2-12 Unit Current Consumption
2-12-1 CPU Rack and Expansion Racks
104
Note
Note When duplex Power Supply Units are used, the load for each CS1D Power
Using Pressure-welded Connector
Connecting Cables:
G79-@@@C-@@@-@@@
XW2Z-@@@
There are fixed amounts of current and power that can be provided to the
Units on the Rack. Even when using only one Power Supply Unit, design the
system so that the total current consumption of Units on the Rack does not
exceed the values for the maximum Power Supply Unit current and the maxi-
mum total power.
Calculate the total current consumption under normal conditions (i.e., with
one Power Supply Unit mounted), taking into account the load when an error
occurs at one of the Power Supply Units. If two different kinds of Power Supply
Units are to be used, calculate the current consumption using the output of
the smaller-capacity Power Supply Unit.
Supply Unit is reduced by approximately half.
The maximum current and power provided for the CPU Rack and Expansion
Racks is shown below.
1. CPU Rack: When making calculations, include the current and power con-
2. When making calculations, include the current and power consumption for
sumption for a CPU Backplane for Duplex CPU System, a Duplex Unit, and
two CS1D Power Supply Units.
an Online Replacement Expansion Backplane.
CS1D-PA207R
CS1D-PD024
CS1D-PD025
Power Supply
Unit model
150
123
7 A
4.3 A
5.3 A
5-V (internal
logic power
supply)
Maximum current provided
1.3 A
0.56 A
1.3 A
26-V (relay
supply)
power
None
None
None
24-V (service
supply)
power
Section 2-12
35 W
28 W
40 W
Maximum
provided
power
total

Related parts for CS1D-DPL02D