4. Connecting a Programming Device
5. Checking Initial Operation
Basic Procedures
!Caution When 200 to 240 V AC power is being supplied, be sure to remove the jumper
!Caution With the default settings, the PLC Setup is set to specify using the mode set
1,2,3...
Note With a Duplex CPU System, operations, such as generating I/O tables and
Note If an inconsistency is detected between the two CS1D CPU Units, a duplex
Connect the CX-Programmer or Programming Console to the active CPU
Unit’s peripheral port (the upper port) or connect the CX-Programmer to the
RS-232C port. (See note.)
transferring the program, will not be possible if the Programming Device is
connected to the standby CPU Unit.
bar that shorts the voltage selector terminals. The Power Supply Unit will be
damaged if 200 to 240 V AC is supplied with the jumper bar connected.
1. Check the power supply wiring and voltage and turn ON the power supply
2. With a Duplex CPU System, confirm that the DPL STATUS indicator on the
verification error will occur and the DPL STATUS indicator will flash red. If this
happens, press the initialization switch. Unless there is a hardware error caus-
ing the inconsistency, the error should be cleared.
3. With a Duplex CPU System, confirm that the ACTIVE indicator on the ac-
on the Programming Console and if a Programming Console is not con-
nected, the CPU Unit will start in RUN mode. Under these conditions, the PLC
will start operation as soon as power is turned ON.
• Turn OFF pin 4 on the DIP switch when connecting a Programming
• Turn ON pin 5 on the DIP switch when connected a Programming Device
Device to the peripheral port. Turn pin 4 ON when connecting any other
device.
other than a Programming Console to the RS-232C port. Turn pin 5 OFF
when connecting any other device.
to the CS1D Power Supply Units. Confirm that the POWER indicator on the
Power Supply Unit when power is turned ON.
front of the Duplex Unit flashes green indicating that duplex operation is
being initialized. If initialization is completed normally, the DPL STATUS in-
dicator will stop flashing and remain lit green.
tive CPU Unit lights green and be sure that the Programming Device is
connected to the active CPU Unit.
Connect to peripheral
or RS-232C port on
active CPU Unit.
SYSMAC
CS1D-CPU67H
PROGRAMMABLE CONTROLLER
MCPWR
PORT
Active CPU Unit
ERR/ALM
PRPHL
RUN
INH
BUSY
BKUP
COMM
DUPLEX
DUPLEX
LEFT CPU
INIT.
RIGHT CPU
DPL SW
ON
ON
SW
SYSMAC
CS1D-CPU67H
PROGRAMMABLE CONTROLLER
MCPWR
PORT
ERR/ALM
PRPHL
RUN
INH
BUSY
BKUP
COMM
CX-Programmer
or
Programming
Console
(peripheral port only)
RUN
MONITOR
PR
PRO27
PR
PROGRAMMING CONSOLE
FUN
AND
OGRAMMING CONSOLE
LD
7
E
B
A
4
1
0
O27
EAR MIC
PROGRAM
SFT
OR
OUT
F
C
8
5
2
NOT
CNT
TIM
D
9
6
3
TR
DM
EXT
LR
CH
HR
Section 4-2
139