Auxiliary Area
Operation Start Time
Operation End Time
Startup Time
Power Interruption Time
Number of Power
Interruptions
Total Power ON Time
Operation Start/Stop Times (CPU Unit Ver. 1.1 or Later Only)
Power Supply Information
Name
Name
A515 to
A517
A518 to
A520
A510 and
A511
A512 and
A513
A514
A523
Address
Address
The time that operation started as a result of changing the
operating mode to RUN or MONITOR mode is stored here in
BCD.
A51500 to A51507: Seconds (00 to 59)
A51508 to A51515: Minutes (00 to 59)
A51600 to A51607: Hour (00 to 23)
A51608 to A51615: Day of month (01 to 31)
A51700 to A51707: Month (01 to 12)
A51708 to A51715: Year (00 to 99)
Note: The previous start time is stored after turning ON the
power supply until operation is started.
The time that operation stopped as a result of changing the
operating mode to PROGRAM mode is stored here in BCD.
A51800 to A51807: Seconds (00 to 59)
A51808 to A51815: Minutes (00 to 59)
A51900 to A51907: Hour (00 to 23)
A51908 to A51915: Day of month (01 to 31)
A52000 to A52007: Month (01 to 12)
A52008 to A52015: Year (00 to 99)
Note: If an error occurs in operation, the time of the error will
be stored. If the operating mode is then changed to PRO-
GRAM mode, the time that PROGRAM mode was entered
will be stored.
These words contain the time (in BCD) at which the power
was turned ON. The contents are updated every time that
the power is turned ON.
A51000 to A51007: Seconds (00 to 59)
A51008 to A51015: Minutes (00 to 59)
A51100 to A51107: Hour (00 to 23)
A51108 to A51115: Day of the month (01 to 31)
These words contain the time (in BCD) at which the power
was interrupted. The contents are updated every time that
the power is interrupted.
A51200 to A51207: Seconds (00 to 59)
A51208 to A51215: Minutes (00 to 59)
A51300 to A51307: Hour (00 to 23)
A51308 to A51315: Day of month (01 to 31)
These words are not cleared when the power supply is
turned ON.
Contains the number of times (in binary) that power has
been interrupted since the power was first turned on. To
reset this value, overwrite the current value with 0000.
Contains the total time (in binary) that the PLC has been on
in 10-hour units. The data is stored is updated every 10
hours. To reset this value, overwrite the current value with
0000.
Description
Description
Section 8-11
Read/write
Read/write
Read/write
Read/write
Read/write
Read/write
Access
Access
285