CS1D-DPL02D Omron, CS1D-DPL02D Datasheet - Page 448

no-image

CS1D-DPL02D

Manufacturer Part Number
CS1D-DPL02D
Description
CS1D Dual IO Exp
Manufacturer
Omron
Datasheet

Specifications of CS1D-DPL02D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
10-2-9 Program Error Check
10-2-10 Cycle Time Overrun Error Check
10-2-11 PLC Setup Setting Error Check
Error Processing
There may be a bug in the program. Check
the program in all tasks. Check FOR/LOOP
and JMP, CJP, and CPN.
PLC Setup setting error occurred.
Program error occurred.
A29511 (No END
A29508 to A29510
from Programming
(instruction error
Error Flag) ON?
PC Setup written
The cycle time was too long.
A29512 (Task
Flag) ON?
flags) ON?
Console?
Anticipated cycle time
less than PLC Setup
monitor setting?
OFF
No
OFF
OFF
ON
Yes
ON
ON
ON
OFF
Task that stopped
program (A294)?
Not #FFFF
#FFFF
The specified task does not exist.
Check the pairing of the TKON and
TKOF instructions.
There is no END(001) in the task that
stopped the program (A294). Add
END(001).
The program was stopped for the PLC Setup
setting to stop the program for instruction
errors. Check the program based on the task
(A294) and address (A298 and A299) that
stopped the program.
Turn the power supply OFF and then back ON
again.
Executing the program resulted in
exceeding the monitor time. Set the
maximum cycle time (Watch Cycle Time)
in the PLC Setup.
The setting indicated by the contents
of A406 is illegal. Check the setting
from a Programming Console.
A communications error may have occurred
during data transfer from the CX-
Programmer. Retransfer the PLC Setup.
Section 10-2
413