CS1D-DPL02D Omron, CS1D-DPL02D Datasheet - Page 473

no-image

CS1D-DPL02D

Manufacturer Part Number
CS1D-DPL02D
Description
CS1D Dual IO Exp
Manufacturer
Omron
Datasheet

Specifications of CS1D-DPL02D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Online Replacement of I/O Units, Special I/O Units, and CPU Bus Units
Related Auxiliary Area Flags
438
A034
A035
A036
A037
A038
A039
A040
A041
A261
Word
00 to 04 Used to confirm when online replacement is in progress for a slot
00 to 08 Used to confirm when online replacement is in progress for a slot
00 to 08 Used to confirm when online replacement is in progress for a slot
00 to 08 Used to confirm when online replacement is in progress for a slot
00 to 08 Used to confirm when online replacement is in progress for a slot
00 to 08 Used to confirm when online replacement is in progress for a slot
00 to 08 Used to confirm when online replacement is in progress for a slot
00 to 08 Used to confirm when online replacement is in progress for a slot
10
Bits
on Rack 0. A bit will be ON when online replacement is in
progress for the corresponding slot. Bits 00 to 04 correspond to
slots 0 to 4.
00: ON when online replacement is in progress for slot 0 on Rack
0.
01: ON when online replacement is in progress for slot 1 on Rack
0.
02: ON when online replacement is in progress for slot 2 on Rack
0.
03: ON when online replacement is in progress for slot 3 on Rack
0.
04: ON when online replacement is in progress for slot 4 on Rack
0.
on Rack 1. A bit will be ON when online replacement is in
progress for the corresponding slot. Bits 00 to 08 correspond to
slots 0 to 8.
on Rack 2. A bit will be ON when online replacement is in
progress for the corresponding slot. Bits 00 to 08 correspond to
slots 0 to 8.
on Rack 3. A bit will be ON when online replacement is in
progress for the corresponding slot. Bits 00 to 08 correspond to
slots 0 to 8.
on Rack 4. A bit will be ON when online replacement is in
progress for the corresponding slot. Bits 00 to 08 correspond to
slots 0 to 8.
on Rack 5. A bit will be ON when online replacement is in
progress for the corresponding slot. Bits 00 to 08 correspond to
slots 0 to 8.
on Rack 6. A bit will be ON when online replacement is in
progress for the corresponding slot. Bits 00 to 08 correspond to
slots 0 to 8.
on Rack 7. A bit will be ON when online replacement is in
progress for the corresponding slot. Bits 00 to 08 correspond to
slots 0 to 8.
ON while an online replacement operation is in progress. Turns
OFF when the operation is completed normally.
INS
Replace End?
~5-8=I32
Replace End
5-8=I32
Description
Section 11-4

Related parts for CS1D-DPL02D