CS1D-DPL02D Omron, CS1D-DPL02D Datasheet - Page 311

no-image

CS1D-DPL02D

Manufacturer Part Number
CS1D-DPL02D
Description
CS1D Dual IO Exp
Manufacturer
Omron
Datasheet

Specifications of CS1D-DPL02D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
276
Auxiliary Area
Time of Switch from Duplex to
Simplex Operation
Duplex Verification Error
Switch Flag
Duplex Bus Error Switch Flag
Duplex Initialization Error
Switch Flag
CPU Unit Setting Switch Flag
CPU Error (WDT) Switch Flag A01904
FALS Instruction Error Switch
Flag
Cycle Time Overrun Switch
Flag
Program Error Switch Flag
Fatal Inner Board Error Switch
Flag (Process-control CPU
Units only)
Memory Error Switch Flag
Time of Previous Switch from
Duplex to Simplex Operation
Time of Switching
Previous Cause of Switching
Previous Time of Switching
Name
Name
Name
A024 to
A026
A01900
A01901
A01902
A01903
A01906
A01908
A01909
A01912
A01915
A020 to
A022
Address
Address
Address
The time when operation was switched from duplex to sim-
plex operation is stored.
The time is cleared when duplex operation is restored.
A02400 to A02407: Seconds (00 to 59)
A02408 to A02415: Minutes (00 to 59)
A02500 to A02507: Hours (00 to 23)
A02508 to A02515: Day of month (01 to 31)
A02600 to A02607: Month (01 to 12)
A02608 to A02615: Year (00 to 99)
ON: A duplex verification error caused the previous switch
from duplex to simplex operation.
ON: A duplex bus error caused the previous switch from
duplex to simplex operation.
ON: An error during duplex initialization caused the previous
switch from duplex to simplex operation and duplex opera-
tion was never started.
ON: Changing the CPU Unit’s switch from USE to NO USE
caused the previous switch from duplex to simplex opera-
tion.
ON: A CPU Unit error (WDT) caused the previous switch
from duplex to simplex operation.
ON: Execution of an FALS instruction caused the previous
switch from duplex to simplex operation.
ON: Exceeding the cycle time caused the previous switch
from duplex to simplex operation.
ON: A program error caused the previous switch from duplex
to simplex operation.
ON: A fatal Inner Board error caused the previous switch
from duplex to simplex operation.
ON: A memory error caused the previous switch from duplex
to simplex operation.
The time of the previous switch from duplex to simplex oper-
ation is stored.
A02000 to A02007: Seconds (00 to 59)
A02008 to A02015: Minutes (00 to 59)
A02100 to A02107: Hours (00 to 23)
A02108 to A02115: Day of month (01 to 31)
A02200 to A02207: Month (01 to 12)
A02208 to A02215: Year (00 to 99)
Description
Description
Description
Section 8-11
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
Read-only
Access
Access
Access

Related parts for CS1D-DPL02D