CS1D-DPL02D Omron, CS1D-DPL02D Datasheet - Page 381

no-image

CS1D-DPL02D

Manufacturer Part Number
CS1D-DPL02D
Description
CS1D Dual IO Exp
Manufacturer
Omron
Datasheet

Specifications of CS1D-DPL02D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Computing the Cycle Time
Parallel Processing with Asynchronous Memory Access (Single CPU Systems Only)
Program Execution Cycle
346
The program execution cycle time depends on the following conditions.
Services Inner Board events (Single CPU
Systems or Process-control CPU Units
only)
Services file access (Memory Card or EM
file memory)
Services communications ports
• Type and number of instructions in the user program (in all cyclic tasks
• Type and number of Basic I/O Units
• Number of SYSMAC BUS Remote I/O Master Units and number of I/O
• Type and number of Special I/O Units, CS-series CPU Bus Units, Inner
• Specific servicing for the following Units/Boards
that are executed during a cycle, and within interrupt tasks for which the
execution conditions have been satisfied).
points on the Slaves
Boards, and type of services being executed.
• Data link refreshing and the number of data link words for Controller
• Remote I/O for DeviceNet (Master) Units and the number of remote
• Use of protocol macros and the largest communications message
• Socket services for specific control bits for Ethernet Units and the num-
Link and SYSMAC LINK Units
I/O words
ber of send/receive words
Details
If a uniform peripheral servicing time
hasn’t been set in the PLC Setup for this
servicing, 4% of the previous cycle’s
cycle time (calculated in step (3)) will be
allowed for peripheral servicing.
If a uniform peripheral servicing time has
been set in the PLC Setup, servicing will
be performed for the set time. At least
0.1 ms, however, will be serviced whether
the peripheral servicing time is set or not.
If no Inner Boards are mounted, the ser-
vicing time is 0 ms.
If a uniform peripheral servicing time
hasn’t been set in the PLC Setup for this
servicing, 4% of the previous cycle’s
cycle time (calculated in step (3)) will be
allowed for peripheral servicing.
If a uniform peripheral servicing time has
been set in the PLC Setup, servicing will
be performed for the set time. At least
0.1 ms, however, will be serviced whether
the peripheral servicing time is set or not.
If there is no file access, the servicing
time is 0 ms.
If a uniform peripheral servicing time
hasn’t been set in the PLC Setup for this
servicing, 4% of the previous cycle’s
cycle time (calculated in step (3)) will be
allowed for peripheral servicing.
If a uniform peripheral servicing time has
been set in the PLC Setup, servicing will
be performed for the set time. At least
0.1 ms, however, will be serviced whether
the peripheral servicing time is set or not.
If no communications ports are used, the
servicing time is 0 ms.
Processing time and fluctuation cause
Section 9-4

Related parts for CS1D-DPL02D