CS1D-DPL02D Omron, CS1D-DPL02D Datasheet - Page 520

no-image

CS1D-DPL02D

Manufacturer Part Number
CS1D-DPL02D
Description
CS1D Dual IO Exp
Manufacturer
Omron
Datasheet

Specifications of CS1D-DPL02D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
CS1W-OD292 Transistor Output Unit (96 Points, Sourcing)
Note The maximum load currents will be 1.0 A/command and 6.0 A/Unit if a pressure-welded connector is
Specifications of Basic I/O Units and High-density I/O Units
Rated Voltage
Operating Load Voltage
Range
Maximum Load Current
Maximum Inrush Current
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
Insulation Resistance
Dielectric Strength
No. of Circuits
Internal Current Consumption 480 mA max. at 5 V DC
Fuses
External Power Supply
Weight
Accessories
Circuit Configuration
Terminal Connections
used.
12 to 24 V DC
10.2 to 26.4 V DC
0.1 A/point, 1.2 A/common, 7.2 A/Unit (See note.)
1.0 A/point, 10 ms max.
8.0 A/common, 10 ms max.
0.1 mA max.
1.5 V max.
0.5 ms max.
1.0 ms max.
20 M between the external terminals and the GR terminal (100 V DC)
1,000 V AC between the external terminals and the GR terminal for 1 minute at a leakage
current of 10 mA max.
96 points (16 points/common, 6 commons)
3 A (1 per common, 6 total)
The fuse cannot be replaced by the user.
10.2 to 26.4 V DC, 100 mA max.
320 g max.
Two connectors for external wiring (soldered)
The ERR indicator will light if a fuse blows or if the external power supply is turned OFF,
and the corresponding Flag in the Basic I/O Unit Information Area (A050 to A089) will turn
ON.
When wiring, pay careful attention to the polarity of the external power supply. The load
may operate if the polarity is reversed.
Indicator
switch circuit
Blown fuse
detection
circuit
Output indicator
ERR indicator
SW
Fuse
OUT15
0 V
COM (+V)
OUT15
0V
OUT00
OUT00
to
to
3 CN1 circuits
3 CN2 circuits
Appendix A
485