CS1D-DPL02D Omron, CS1D-DPL02D Datasheet - Page 239

no-image

CS1D-DPL02D

Manufacturer Part Number
CS1D-DPL02D
Description
CS1D Dual IO Exp
Manufacturer
Omron
Datasheet

Specifications of CS1D-DPL02D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Specific PLC Setup Settings
Baud Rate (bps)
No-protocol Settings
Delay
Start Code/End Code
204
161
162
164
165
Word
Word
Word
Programming
Programming
Programming
Address in
Address in
Address in
Console
Console
Console
0 to 7
0 to 15
8 to 15
0 to 7
12
8 and 9
0 to 7
Bit(s)
Bit(s)
Bit(s)
00 hex: 9,600
06 hex: 9,600
07 hex: 19,200
08 hex: 38,400
09 hex: 57,600
0A hex: 115,200
(Unit: bps)
Default: 00 hex
0000 to 270F hex:
0 to 99990 ms (10-
ms units)
Default: 0000 hex
00 to FF hex
Default: 00 hex
00 to FF hex
Default: 00 hex
0: None
1: Code in 164
Default: 0
0 hex: None
1 hex: Code in 164
2 hex: CR+LF
Default: 0 hex
00 hex:
256 bytes
01 to FF hex:
1 to 255 bytes
Default: 00 hex
Settings
Settings
Settings
Settings 00 hex and 06 hex through 0A hex
are valid when the communications mode is
set to peripheral bus.
This setting determines the delay from exe-
cution of TXD(236) until the data is actually
transmitted from the specified port.
Start code: Set this start code only when the
start code is enabled (1) in bits 12 of 165.
End code: Set this end code only when the
end code is enabled (1) in bits 8 and 9 of
165.
Start code setting:
A setting of 1 enables the start code in 164
bits 8 to 15.
End code setting:
With a setting of 0, the amount of data being
received must be specified. A setting of 1
enables the end code in bits 0 to 7 of 164. A
setting of 2 enables an end code of CR+LF.
Set the data length to be sent and received
with no-protocol communications. The end
code and start code are not included in the
data length.
Set this value only when the end code set-
ting in bits 8 and of 165 is “0 hex: None.”
This setting can be used to change the
amount of data that can be transferred at
one time by TXD(236) or RXD(235). The
default setting is the maximum value of 256
bytes.
Function
Function
Function
A61902
(RS-232C
Port Settings
Changing
Flag)
A61902
(RS-232C
Port Settings
Changing
Flag)
A61902
(RS-232C
Port Settings
Changing
Flag)
flags and
flags and
flags and
Related
Related
Related
words
words
words
Section 6-2
Takes effect
the next
cycle.
(Also can be
changed with
STUP (237).)
Takes effect
the next
cycle.
(Also can be
changed with
STUP (237).)
Takes effect
the next
cycle.
(Also can be
changed with
STUP (237).)
ting’s effec-
ting’s effec-
ting’s effec-
New set-
New set-
New set-
tiveness
tiveness
tiveness