CS1D-DPL02D Omron, CS1D-DPL02D Datasheet - Page 462

no-image

CS1D-DPL02D

Manufacturer Part Number
CS1D-DPL02D
Description
CS1D Dual IO Exp
Manufacturer
Omron
Datasheet

Specifications of CS1D-DPL02D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Low Battery Indicators
Replacing User-serviceable Parts
CS1D-CPU@@H
CS1D-CPU6@S
CS1D-CPU4@S
Model
0%
30%
50%
70%
100%
0%
30%
50%
70%
100%
power is ON
Time that
CPU Unit
Note
626 days (1 yr, 8 mo)
886 days (2 yr, 5 mo)
1,225 days (3 yr, 4 mo) 1,825 days (5 yr)
1,825 days (5 yr)
1,825 days (5 yr)
780 days (2 yr, 1 mo)
1,101 days (3 yr)
1,519 days (4 yr, 1 mo) 1,825 days (5 yr)
1,825 days (5 yr)
1,825 days (5 yr)
The time that CPU power is ON shown in the following table (power supply
rate) is calculated as follows:
Power supply rate =
The following table shows minimum lifetimes and typical lifetimes for the
backup battery.
1. The minimum lifetime is the memory backup time at an ambient tempera-
2. There is no difference between the minimum lifetimes and the minimum
3. The battery lifetime and low battery voltage detection will vary under appli-
If the PLC Setup has been set to detect a low-battery error, the ERR/ALM
indicator on the front of the CPU Unit will flash when the CPU Unit detects that
the battery is nearly discharged.
Minimum lifetime
ture of 55 C. The typical lifetime is the memory backup time at an ambient
temperature of 25 C.
times to battery error detection.
cation at high power-supply rates.
2000
1800
1600
1400
1200
1000
Total time power is ON/(total time power is ON + total time power is OFF)
800
600
400
200
0
0
20
1,825 days (5 yr)
1,825 days (5 yr)
1,825 days (5 yr)
1,825 days (5 yr)
1,825 days (5 yr)
1,825 days (5 yr)
1,825 days (5 yr)
1,825 days (5 yr)
Typical lifetime
CS1D-CPU@@H/CPU6@S (Minimum lifetime)
CS1D-CPU@@H/CPU6@S (Typical lifetime)
CS1D-CPU4@S (Minimum lifetime)
CS1D-CPU4@S (Typical lifetime)
Power-supply rate (%)
40
60
626 days
886 days
1,225 days
1,825 days
1,825 days
780 days
1,101 days
1,519 days
1,825 days
1,825 days
Min. time for
battery error
detection
80
5 days
5 days
5 days
5 days
5 days
5 days
5 days
5 days
5 days
5 days
complete discharge
Time from battery
error detection to
100
Section 11-2
427