Specifications of CS1D-DPL02D

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Specific PLC Setup Settings
Power OFF Detection Time (Power OFF Detection Delay Time)
Power OFF Interrupt Disable (Single CPU Systems Only)
6-2-4
198
225
225
Word
Word
Programming
Programming
Address in
Address in
Console
Console
0 to 7
15
SIOU Refresh Tab Page
Bit(s)
Bit(s)
00 to 0A hex:
0 to 10 ms
(1-ms units)
Default: 00 hex
0: Disabled
1: Enabled
Default: 0
Note Single CPU Systems only.
Note This setting cannot be used with Duplex CPU Systems.
Settings
Settings
This setting determines how much of a
delay there will be from the detection of a
power interruption (approximately 10 to
25 ms for AC power and 2 to 5 ms for DC
power after the power supply voltage drops
below 85% of the rated value) to the confir-
mation of a power interruption. The default
setting is 0 ms.
If enabled, the power OFF interrupt will be
executed after a power interruption is con-
firmed (see note). If the power OFF interrupt
is not enabled, the CPU Unit will be reset
and operation will stop.
When this setting is set to 1, the power OFF
interrupt task will be executed when power
is interrupted.
Function
Function
---
---
flags and
flags and
Related
Related
words
words
Section 6-2
At startup or
at the start of
operation.
(Can’t be
changed dur-
ing opera-
tion.)
Takes effect
at startup or
at the start of
operation.
(Can’t be
changed dur-
ing opera-
tion.)
ting’s effec-
ting’s effec-
New set-
New set-
tiveness
tiveness