FX1S-30MR-ES/UL MITSUBISHI, FX1S-30MR-ES/UL Datasheet - Page 87

PLC, 16 IN, 14 RELAY OUT, 110V/2

FX1S-30MR-ES/UL

Manufacturer Part Number
FX1S-30MR-ES/UL
Description
PLC, 16 IN, 14 RELAY OUT, 110V/2
Manufacturer
MITSUBISHI
Datasheet

Specifications of FX1S-30MR-ES/UL

No. Of Analogue Inputs
16
No. Of Analogue Outputs
14
Ip/nema Rating
IP10
Approval Bodies
CE, CUL, UL
External Depth
49mm
External Length / Height
90mm
External Width
60mm
Mounting Type
Panel
4.6.3
4.6.4
FX Series Programmable Controllers
Disabling Individual Interrupts
Individual interrupt devices can be temporarily or permanently disabled by driving an
associated special auxiliary relay. The relevant coils are identified in the tables of devices in
chapter 6. However for all PLC types the head address is M8050, this will disable interrupt
I0
Driving special auxiliary relays:
Disabling high speed counter interrupts
Counter Interrupts
Identification of interrupt pointer number:
Example:
Additional notes:
• Never drive a special auxiliary coil without first checking its use. Not all PLC’s assign the
• These interrupts can only be disabled as a single group by driving M8059 ON.
• Please see the following pages for more details on the HSSC applied instruction.
M8000
I 0 0
- High Speed Counter Set, HSCS FNC 53 - see page 5-55
.
same use to the same auxiliary coils.
Further details about counter interrupts can be found in the following section.
DHSCS
Counter interrupt number 6 points (1 to 6). Counter interrupts can be
entered as the output devices for High Speed Counter Set (HSCS, FNC
53). To disable the Counter Interrupts Special Auxiliary Relay M8059
must be set ON.
K100
C255 I030
The sequence programmed after the label
(indicated by the I030 pointer) is executed once
t h e v a lu e o f H i g h S p e e d C o u n te r C 2 5 5
reac hes/equa ls th e prese t limit of K 100
identified in the example HSCS.
Devices in Detail 4
4-13