5.10.10 INT (FNC 129)
FX Series Programmable Controlers
Points to note:
a) The source data is always a double (32 bit) word; a floating point value.
b) This instruction is the inverse of the FLT instruction. (See page 5-49)
c) If the result is 0 then the zero flag M8020 is set ON.
INT
FNC 129
(Float to
Integer)
Mnemonic
For single word (16 bit) operation the destination is a 16 bit value.
For double word (32 bit) operation the destination is a 32 bit value.
If the source data is not a whole number it must be rounded down. In this case the borrow
flag M8021 is set ON to indicate a rounded value.
If the resulting integer value is outside the valid range for the destination device then an
overflow occurs. In this case the carry flag M8022 is set on to indicate overflow.
Note: If overflow occurs, the value in the destination device will not be valid.
Converts a
number from
floating point
format to decimal
format
Function
D - must be in floating
point number format
(always 32 bits).
S
Operation:
The floating point value of S is rounded down to
the nearest integer value and stored in normal
binary format in D.
Operands
D - decimal format
for INT, INTP - 16 bits
for DINT, DINTP - 32
bits
D
Applied Instructions 5
INT, INTP:
5 steps
DINT, DINTP:
9 steps
Program steps
5-116