FX1S-30MR-ES/UL MITSUBISHI, FX1S-30MR-ES/UL Datasheet - Page 58

PLC, 16 IN, 14 RELAY OUT, 110V/2

FX1S-30MR-ES/UL

Manufacturer Part Number
FX1S-30MR-ES/UL
Description
PLC, 16 IN, 14 RELAY OUT, 110V/2
Manufacturer
MITSUBISHI
Datasheet

Specifications of FX1S-30MR-ES/UL

No. Of Analogue Inputs
16
No. Of Analogue Outputs
14
Ip/nema Rating
IP10
Approval Bodies
CE, CUL, UL
External Depth
49mm
External Length / Height
90mm
External Width
60mm
Mounting Type
Panel
3.4.2
FX Series Programmable Controllers
Using OUT to drive an STL coil
This has the same operational features as using SET. However, there is one major function
which SET is not used. This is to make what is termed ‘distant jumps’.
OUT is used for loops and jumps
If a user wishes to ‘jump’ back up a program,
i.e. go back to a state which has already been
processed, the OUT instruction would be used
with the appropriate STL state number.
Alternatively the user may wish to make a
large ‘jump’ forwards skipping a whole section
of STL programmed states.
Out is used for distant jumps
If a step in one STL program flow was required
to trigger a step in a second, separate STL
program flow the OUT instruction would be
used.
Note: Although it is possible to use SET for jumps and loops use of OUT is needed for
display of STL in SFC like structured format.
Partial
repeat
OUT
STL
flow 1
S 20
S 21
S 22
S 23
S 0
S 20
S 21
S 22
S 23
S 0
OUT
STL
flow 2
OUT
STL Programming 3
S 40
S 41
S 42
S 43
S 44
S 1
S 20
S 21
S 22
S 23
S 0
3-6
Program
jump

Related parts for FX1S-30MR-ES/UL