FX1S-30MR-ES/UL MITSUBISHI, FX1S-30MR-ES/UL Datasheet - Page 107

PLC, 16 IN, 14 RELAY OUT, 110V/2

FX1S-30MR-ES/UL

Manufacturer Part Number
FX1S-30MR-ES/UL
Description
PLC, 16 IN, 14 RELAY OUT, 110V/2
Manufacturer
MITSUBISHI
Datasheet

Specifications of FX1S-30MR-ES/UL

No. Of Analogue Inputs
16
No. Of Analogue Outputs
14
Ip/nema Rating
IP10
Approval Bodies
CE, CUL, UL
External Depth
49mm
External Length / Height
90mm
External Width
60mm
Mounting Type
Panel
4.12.4
FX Series Programmable Controllers
File Registers
Program memory registers
File registers can be secured in the program memory (EEPROM or EPROM) in units of 500
points. These registers can be accessed with a peripheral device. While the PLC is operating,
data in the file registers can be read to the general-use/ battery backed/ latched registers by
using the BMOV instruction.
File registers are actually setup in the parameter area of the PLC. For every block of 500 file
registers allocated and equivalent block of 500 program steps are lost.
Note: The device range for file registers in the FX
data registers. The allocation of these devices as file registers ensures that the data is kept
with the program.
Writing to file registers:
Special caution when using FX
Available devices:
• FX
• FX
• No file registers can be modified during RUN.
• Please refer to the table on page 4-33 or chapters 6 and 8, where further details of the
programmer or a personal computer running the appropriate software.
For details of how to carry out the changes please reference the relevant operation
manual for guidance.
BMOV instruction.
availability of devices can be found.
1S
1N
, FX
file register data can only be changed by a peripheral device such as a hand held
2N
and FX
2NC
file register data can also be changed by the program using the
1S
:
1N
, FX
2N
and FX
2NC
overlaps with the latched
Devices in Detail 4
4-33