FX1S-30MR-ES/UL MITSUBISHI, FX1S-30MR-ES/UL Datasheet - Page 148

PLC, 16 IN, 14 RELAY OUT, 110V/2

FX1S-30MR-ES/UL

Manufacturer Part Number
FX1S-30MR-ES/UL
Description
PLC, 16 IN, 14 RELAY OUT, 110V/2
Manufacturer
MITSUBISHI
Datasheet

Specifications of FX1S-30MR-ES/UL

No. Of Analogue Inputs
16
No. Of Analogue Outputs
14
Ip/nema Rating
IP10
Approval Bodies
CE, CUL, UL
External Depth
49mm
External Length / Height
90mm
External Width
60mm
Mounting Type
Panel
5.3.2
FX Series Programmable Controlers
SUB (FNC 21)
in the destination device D. Note: the ‘Points to note’, under the ADD instruction (previous
page) can also be similarly applied to the subtract instruction.
SUB
FNC 21
(Subtract)
Mnemonic
X0
SUB
One source
device
is subtracted from
the other - the
result is stored in
the destination
device
Function
[ S1 ]
D 10 D 12
[ S2 ]
[ D ]
D 14
K, H, KnX, KnY, KnM, KnS,
T, C, D, V, Z
When using M8023 to subtract floating point
data, only double word (32 bit) data registers
(D) or constants (K/H) may be used. See page
4-46 for more details regarding floating point
format.
S
1
Operation : (Applicable to all units)
The data contained within the source device, S
subtracted from the contents of source device S
The result or remainder of this calculation is stored
Operands
S
2
KnY, KnM, KnS,
T, C, D, V, Z
D
Applied Instructions 5
SUB, SUBP:
7steps
DSUB,
DSUBP:
13 steps
Program steps
5-26
2
is
1
.