3.4
3.4.1
FX Series Programmable Controllers
Moving Between STL Steps
To activate an STL step the user must first drive the state coil. Setting the coil has already
been identified as a way to start an STL program, i.e. drive an initial state. It was also noted
that using an OUT statement to driving a state coil has a different meaning to the SET
instruction. These difference will now be explained:
Using SET to drive an STL coil
• SET is used to drive an STL state coil to make the step active. Once the current STL step
Note: If a user wishes to forcibly reset an
40) instructions would perform this task.
STL step, using the RST or ZRST (FNC
activates a second following step, the source STL coil is reset. Hence, although SET is
used to activate a state the resetting is automatic.
However, if an STL state is driven by a
series of standard ladder logic instructions,
i .e . n o t a p r e c e d i n g S T L s ta t e , t h e n
standard programming rules apply.
In the example shown opposite S20 is not
reset even after S30 or S21 have been
driven. In addition, if S20 is turned OFF,
S 3 0 w ill a ls o st o p o pe r a tin g . T h is is
because S20 has not been used as an STL
state. The first instruction involving the
status of S20 is a standard LoaD instruction and NOT an STL instruction.
• SET is used to drive an immediately following STL step which typically will have a larger
• SET is used to drive STL states which occur within the enclosed STL program flow, i.e.
STL state number than the current step.
SET is not used to activate a state which appears in an unconnected, second STL flow
diagram.
X000
S020
X000
S040
ZRST S21 S28
STL Programming 3
SET S021
RST S022
3-5
S020
S030