FX1S-30MR-ES/UL MITSUBISHI, FX1S-30MR-ES/UL Datasheet - Page 134

PLC, 16 IN, 14 RELAY OUT, 110V/2

FX1S-30MR-ES/UL

Manufacturer Part Number
FX1S-30MR-ES/UL
Description
PLC, 16 IN, 14 RELAY OUT, 110V/2
Manufacturer
MITSUBISHI
Datasheet

Specifications of FX1S-30MR-ES/UL

No. Of Analogue Inputs
16
No. Of Analogue Outputs
14
Ip/nema Rating
IP10
Approval Bodies
CE, CUL, UL
External Depth
49mm
External Length / Height
90mm
External Width
60mm
Mounting Type
Panel
5.1.6
FX Series Programmable Controlers
WDT (FNC 07)
there is an error at some point. The PLC will then cease operation to prevent any further errors
from occurring. By causing the watchdog timer to refresh (driving the WDT instruction) the
usable scan (program operation) time is effectively increased.
Points to note:
a) When the WDT instruction is used it will operate on every program scan so long as its input
b) The watchdog timer has a default setting of 200
WDT
FNC 07
(Watch dog
timer refresh)
Mnemonic
condition has been made.
To force the WDT instruction to operate for only ONE scan requires the user to program
some form of interlock.
msec. This time limit may be customized to a
users own requirement by editing the contents of
data register D8000, the watchdog timer register.
Used to refresh
the watch dog
timer during a
program scan
Function
N/A
Can be driven at any time within the main
program body
Operation:
The WDT instruction refreshes the PLC’s watchdog
timer. The watchdog timer checks that the program
scan (operation) time does not exceed an arbitrary time
limit. It is assumed that if this time limit is exceeded
Operands
D
Applied Instructions 5
WDT, WDTP:
1 step
Program steps
5-12