FX1S-30MR-ES/UL MITSUBISHI, FX1S-30MR-ES/UL Datasheet - Page 261

PLC, 16 IN, 14 RELAY OUT, 110V/2

FX1S-30MR-ES/UL

Manufacturer Part Number
FX1S-30MR-ES/UL
Description
PLC, 16 IN, 14 RELAY OUT, 110V/2
Manufacturer
MITSUBISHI
Datasheet

Specifications of FX1S-30MR-ES/UL

No. Of Analogue Inputs
16
No. Of Analogue Outputs
14
Ip/nema Rating
IP10
Approval Bodies
CE, CUL, UL
External Depth
49mm
External Length / Height
90mm
External Width
60mm
Mounting Type
Panel
5.14.3
FX Series Programmable Controlers
TADD (FNC 162)
Points to note:
a) The addition is performed according to standard time values. Hours, minutes and seconds
b) If the addition of the two times results in a value greater than 24 hours, the value of the
c) If the addition of the two times results in a value of zero (0:00:00: 0 hours, 0 minutes, 0
d) The same device may be used as a source (S1 or S2) and destination device. In this case
TADD
FNC 162
(Time
Addition)
Mnemonic
are kept within correct limits. Any overflow is correctly processed.
result is the time remaining above 24 hours.
When this happens the carry flag M8022 is set ON.
seconds) then the zero flag M8020 is set ON.
the addition is continually executed; the destination value changing each program scan. To
prevent this from happening, use the pulse modifier or an interlock program.
Adds two time
values together to
give a new time
Function
D10: 10 hours
D11: 17 mins
D12: 29 secs
D10: 10 hours
D11: 30 mins
D12: 27 secs
10:17:29
10:30:29
S
S
1
1
T, C, D
Note: 3 consecutive devices are used to represent
hours, minutes and seconds respectively.
+
+
D20: 18 hours
D21: 12 mins
D22: 34 secs
D20: 30 hours
D21: 10 mins
D22: 49 secs
S
1
18:12:34
03:10:49
S
S
2
Contents:
Each of S
data devices to be used a time value.
The time value in S
S
2
2
, the result is stored to D as a new time value.
Operands
=
=
S
1
2
, S
D30: 13 hours
D31: 41 mins
D32: 16 secs
D30: 13 hours
D31: 41 mins
D32: 16 secs
2
M8022 ON
04:30:03
13:41:16
and D specify the head address of 3
D
D
1
is added to the time value in
D
Applied Instructions 5
TADD,
TADDP:
7 steps
Program steps
5-139

Related parts for FX1S-30MR-ES/UL