FX1S-30MR-ES/UL MITSUBISHI, FX1S-30MR-ES/UL Datasheet - Page 284

PLC, 16 IN, 14 RELAY OUT, 110V/2

FX1S-30MR-ES/UL

Manufacturer Part Number
FX1S-30MR-ES/UL
Description
PLC, 16 IN, 14 RELAY OUT, 110V/2
Manufacturer
MITSUBISHI
Datasheet

Specifications of FX1S-30MR-ES/UL

No. Of Analogue Inputs
16
No. Of Analogue Outputs
14
Ip/nema Rating
IP10
Approval Bodies
CE, CUL, UL
External Depth
49mm
External Length / Height
90mm
External Width
60mm
Mounting Type
Panel
6.5
FX Series Programmable Controller
Step Ladder (STL) Flags
(M8040 to M8049 and D8040 to D8049)
For symbol key see page 6-1.
General note:
M8040 ( )
STL transfer
disable
M8041 ( S)
Transfer start
M8042 ( )
Start pulse
M8043 ( S)
Zero return
complete
M8044 ( S)
Zero point
condition
M8045 ( )
All output
reset disable
M8046 ( )
STL state ON
M8047 ( )
Enable STL
monitoring
M8048 ( )
Annunciator
ON (Not FX
FX
M8049 ( )
Enable
Annunciator
monitoring
(Not FX
FX
Diagnostic
• All STL states are updated when the END instruction is executed.
1N
1N
Device
)
)
1S
,
1S
,
When ON STL state trans-
fer is disabled
When ON STL transfer from
initial state is enabled dur-
ing automatic operation
(ref. IST FNC 60)
A pulse output is given in
response to a start input
(ref. IST FNC 60)
On during the last state of
ZERO RETURN mode
(ref. IST FNC 60)
ON when the machine zero
is detected
(ref. IST FNC 60)
Disables the ‘all output reset’
function when the operation
mode is changed
(ref. IST FNC 60)
ON when STL monitoring
has been enabled (M8047)
and there is an active STL
state
When ON D8040 to D8047
are enabled for active STL
step monitoring
ON when Annunciator moni-
toring has been enabled
(M8049) and there is an
active Annunciator flag
When ON D8049 is enabled
for active Annunciator state
monitoring
Operation
D8040 ( )
Lowest active
STL step
D8041 ( )
2nd active
STL state
D8042 ( )
3rd active
STL state
D8043 ( )
4th active STL
state
D8044 ( )
5th active STL
state
D8045 ( )
6th active STL
state
D8046 ( )
7th active STL
state
D8047 ( )
8th active STL
state
D8048
D8049 ( )
Lowest active
Annunciator
(Not FX
FX
Diagnostic
1N
Device
)
1S
,
Up to 8 active STL states,
from the range S0 to S899,
are stored in D8040 to D8047
in ascending numerical order.
(Updated at END)
Reserved
Stores the lowest currently
active Annunciator from the
range S900 to S999
(Updated at END)
Diagnostic Devices 6
Operation
6-6

Related parts for FX1S-30MR-ES/UL