Design
• Use a ground board as shown in the diagram and ground (FG) each Unit to one point on the ground
• Do not bundle the ground together with the power supply, motor drive, or Resolver signal wires or run
• If using metal conduit or running wires through metal duct, ground the metal to one point.
Note To make the 3F88L-160/162 Cam Positioner conform to EC Directives, be sure to install the Unit
D External Wiring
• Use a different cable for the Cam Positioner I/O and the control wire. Do not run these wires through
• It is recommended that the Cam Positioner cables and other control and power cables are wired as
• Parallel cable racks must be a minimum of 300 mm apart.
• If multiple terminals are to be housed in one duct, shield the terminals with a grounded conductive
Note The 3F88L-160/162 conforms to the Common Emission Standard (EN50081-2) in relation to
H Points to Consider when Wiring to Peripheral Devices
• Install a surge absorber and noise filter on the AC power supply input wiring.
• Pay attention to the following points when using relays, electromagnetic valves, and other noise-gen-
board.
the ground through the same duct as these wires.
the same cable.
shown below.
plate.
erating devices.
S Separate noise-generating devices, parts and the wiring as much as possible.
S Use a separate power supply system.
within a control panel.
EMI. However, the radiated emission (10-m regulations) may vary depending on the configura-
tion of the control panel, connected devices, wiring, and other conditions. The customer must,
therefore, confirm that devices and the overall machine conform to EC Directives.
1
1
Low-current
cable
Control cable
Power cable
2
3
4
2
Ground to 100 Ω or less
3
Conductive
plate (steel)
300 mm min.
300 mm min.
Ground to 100 Ω or less
4
1. Resolver cable
2. Cam Positioner input cable
3. Cam Positioner power supply cable
4. Power cable
General control cable
Conductive
plate (steel)
200 mm min.
Chapter 2