Communications Unit Flags, Control Bits, and Status Information
Local Data Link Participation Status: IR 90 (See page 307.)
Data Link Status: IR 91 to IR 93 (See pages 158, 307.)
When the first data link status word is not set or is set to the default (0000) for either the manually set data link
tables or automatically set data link tables, the data link status is stored in the following words for nodes 1 to 6
only.
Terminating Resistance Status: IR 95 (See page 310.)
360
Memory Areas
IR 91
IR 92
IR 93
Node 2
Node 4
Node 6
Node 1
Node 3
Node 5
1: Local node data link participating
0: Local node data link not participating or data link
inactive
Terminating resistance status: 0: OFF
Remaining receive area
0: Not remaining
1: Remaining
Insufficient (short) receive area
0: Sufficient
1: Insufficient
Offset error
0: Normal
1: Error
Data link participation
0: Not in data link or data link inactive
1: In data link
Communications error (data link reception)
0: Normal
1: Error
PLC's CPU Unit error
0: Normal
1: Error
PLC status
0: Inactive (user program not running)
1: Active (user program running)
1: ON
Error: Offset exceeds
number of send words.
Remaining: Receive
area is larger than send
area. Data is received
and remaining words
are cleared.
Insufficient: Receive
area is smaller than
send area. Excess data
is truncated; other data
is received.