RECV
170
Introduction
@RECV(98)
D
C
S
Destination node M
01 to 20 (Hex): 1 to 32 (or 01 to 3E (Hex): 1 to 62)
The range of node addresses will vary for networks
other than Controller Link Networks.
C+1
C+2
S: Source node beginning send word
D: Destination node beginning receive word
C: Source node first control data word
C
15
15
15
0
Note
"m" number of send words
0000 to 03DE (Hex): 1 to 990 words
11
11
0
8 7
8 7
Destination network address
00 (Hex): Local network
01 to 7F (Hex): 1 to 127
2. With the message service, there is no guarantee that a message to a des-
3. If the total number of data link words is increased, the communications cy-
RECV receives “m” words beginning with S (the beginning word for data
transmission at the destination node, M) to the words beginning with D (the
beginning word for data reception at the source node).
1. When communicating with a CVM1 or CV-series PLC manufactured prior
2. With the message service, there is no guarantee that a message to a des-
Destination unit address
00 (Hex):
01 to 0F (Hex): Computer (user program)
10 to 1F (Hex): Unit nos. 0 to 15
E1 (Hex):
FE (Hex):
tination node will reach its destination. It is always possible that the mes-
sage may be lost in transit due to noise or some other condition. When
using the message service, it is advisable to prevent this situation from oc-
curring by performing resend processing at the node where instructions
are issued. With the SEND, RECV, and CMND instructions, resend pro-
cessing is performed automatically once the number of retries has been
set, so be sure to specify a number other than “0” for the number of retries.
cle time will be increased. This may cause timeout errors to occur when
waiting for the response. In that case, lengthen the response monitor time
(control data word C+4).
to April 1996 on the local network, the local network address cannot be set
to “00.” Set a number other than “00” as the local network address in the
routing tables, and then specify that number.
tination node will reach its destination. It is always possible that the mes-
sage may be lost in transit due to noise or some other condition. When
0
0
0
PLC's CPU Unit
Inner Board
Unit connected to network
(02 to 0F (Hex) are used
when using Controller Link
Support Boards for PCI Bus
only.)
D
m
C+3
C+4
15
Source node
15
0: Response required
1: Response not required
0
10 8 7
0
Communication port No.
0 to 7
Response monitor time
0000 (Hex): 2 s
0001 to FFFF (Hex): 0.1 to 6,553.5 s
(Unit: 0.1 s)
If the baud rate is slow, then setting a small
value may generate an error. The standard is
approximately 4 seconds at 1 Mbps or 8
seconds at 500 Kbps.
0
3
"m" num-
ber of
send
words
Destination node M
Number of retries
0
0 to F (Hex): 0 to 15 retries
S
15
Section 6-1
0