Communications Cycle Time
8-1-4
8-2
8-2-1
Communications Cycle Time
Specifying Network Parameters
Active Data Links
Note
The network parameters can be specified from the Controller Link Support
Software. This section describes only the allowable setting range for each net-
work parameter. Refer to the Controller Link Support Software Operation
Manual (W308) for setting procedures.
The following table shows the setting range and default for network parame-
ters.
The network parameters become valid immediately after being set.
1. The setting range will be 2 to 62 and the default value will be 62 when the
2. Always stop the data link before changing network parameters.
3. Specify a value for the maximum node address that is equal to or greater
4. For the CVM1 and CV-series PLCs, always set the System Protect Key
5. The maximum node address cannot be changed to 32 when the Wired
This section describes how to calculate the communications cycle time.
The following equations are used to calculate the communications cycle time
when data links are operating.
Wired Systems
Maximum node address
Number of polled nodes per communications cycle
Maximum no. of event-frames per communications
cycle
2 Mbps
1 Mbps
500 Kbps
Baud rate
Wired Network 62 Node Enable Bit in the DM Parameter Area software
switches of the CS1W-CLK21-V1, CS1W-CLK23, CJ1W-CLK21-V1, or
CJ1W-CLK23 Unit is ON and the Unit is restarted.
than the maximum node address in the Controller Link Network.
Switch on the CPU Unit to NORMAL. Otherwise, the network parameter
settings will not be stored normally.
Network 62 Node Enable Bit is ON in the DM Parameter Area software
switches of a CS1W-CLK23, CJ1W-CLK23, CS1W-CLK21-V1, or CJ1W-
CLK21-V1 Unit with unit version 1.2 or later.
Note A: Total number of data link words within the network
B: Number of polled nodes per comm cycle
C: Number of nodes connected to the network
D: Number of nodes that send messages during the
E: Total number of bytes in messages transmitted during the
(total number of words in send areas of all nodes)
(value specified in the network parameters)
communications cycle
communications cycle
10 × A + 600 × B + 290 × C + 320 × D + 4 × E + 3,290 (µs)
18 × A + 1,150 × B + 370 × C + 360 × D + 8 × E + 3,770 (µs)
34 × A + 2,260 × B + 530 × C + 440 × D + 16 × E + 4,730 (µs)
Network parameter
Equation
2 to 32
(See note 1.)
1 to 31
6 to 238
Setting
range
Section 8-2
32
(See note 1.)
4
35
Default
value
255