CV500BI111 Omron, CV500BI111 Datasheet - Page 327

no-image

CV500BI111

Manufacturer Part Number
CV500BI111
Description
Programmable Logic Controller
Manufacturer
Omron
Datasheet

Specifications of CV500BI111

Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
9-2-3
Status Area
Error Information: CIO 1500 + 25 × (Unit No.)
Polling Node Address, Startup Node Address: CIO 1500 + 25 × (Unit No.) + 1
Network Participation Status: CIO 1500 + 25 × (Unit No.) + 2, + 3
Local Data Link Participation Status: CIO 1500 + 25 × (Unit No.) + 6
302
Status Area and Troubleshooting
CVM1 and CV-series Controller Link Units
Note Data link status is valid only when the local node is participating in the data
The status of the Unit and Network is indicated in the following manner in the
PLC.
link. Confirm that the Local Data Link Active Bit is ON before referencing the
data link status.
+ 2
+ 3
Polling node address
Each node address is displayed in 2-digit BCD.
The numbers in the squares indicate node addresses.
The corresponding node participation status is as follows:
0: Not part of the network
1: Part of the network
1: Local node data link participating
0: Local node data link not participating or data link
inactive
1: Network parameter error (In PLC's EEPROM)
1: Data link table error (in PLC's EEPROM)
1: Routing table error (in PLC's EEPROM)
1: PLC system setting error
1: EEPROM error
1: Duplicate node address setting error
1: Inconsistent network parameters
1: Communications controller send error
1: Error log exists
Startup node address
Section 9-2