Error Log
0101
Hex
0103
Hex
0104
Hex
0105
Hex
0106
Hex
0107
Hex
0108
Hex
Error
code
Transmission failed; local node
not in Network
Transmission failed; retry count
exceeded
Transmission failed; maximum
number of frames exceeded.
Transmission failed; node
address incorrect
Transmission failed; redundant
node address
Transmission failed; destination
node not in Network
Transmission failed; specified
Unit does not exist
Contents
Command block
Bits 0 to 7:
Bits 8 to 14:
Bit 15:
Response block
Bits 0 to 7:
Bits 8 to 14:
Bit 15:
(1st byte: bits 8 to 15;
2nd byte, bits 0 to 7)
Source node address
Source Network
address
OFF
Destination node
address
Destination Network
address
ON
1st byte
Detail code
2nd byte
Refer to page 274
Troubleshooting
Using Indicators and
place the local node
into Network.
Using the Controller
Link Support Soft-
ware or FINS
commands, run
echoback test and
check operating envi-
ronment if errors
occur.
Reduce the number
of events per com-
munications cycle or
increase the maxi-
mum number of
network parameter
frames.
Refer to 4-2 CJ-
series Controller Link
Units or 4-4 CVM1
and CV-series Con-
troller Link Units and
check node address
settings to be sure
they are within range
and unique.
Correct node
addresses so that
they are unique
within the same
Network.
Refer to 9-1 Trouble-
shooting Using Indi-
cators and place
destination node into
Network.
Refer to 4-4 CVM1
and CV-series Con-
troller Link Units and
check unit address
and unit number of
destination.
Correction
No
No
No
No
No
No
No
Written to
EEPROM
Section 9-3
All
All
All
All
All
All
All
Applicable
PLC
313