CV500BI111 Omron, CV500BI111 Datasheet - Page 144

no-image

CV500BI111

Manufacturer Part Number
CV500BI111
Description
Programmable Logic Controller
Manufacturer
Omron
Datasheet

Specifications of CV500BI111

Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Setting Data Links
C200HX/HG/HE PLCs
Area 2 Data link
PLC model
Nodes
Setting item
Setting item
Note a) The total number of words in data link send and receive areas
start word
Number of
words
Offset
b) The following values must be satisfied for each node for the data
c) Refer to the Controller Link Support Boards Operation Manual
d) If CX-Net detects an error during the data link table check, trou-
must not exceed 20,000 per node when using Controller Link
Units with unit Ver. 1.2 or later, or 12,000 words per node if using
pre-Ver. 1.2 Controller Link Units.
link area 1 and area 2 so that the final word in the data link does
not go beyond the last word in the PLC memory area.
(Data link start word – 1) + (Total number of send/receive
words in area 1 or area 2)
(W307) for information on the Controller Link Support Board.
bleshoot the error referring to 9-4 Troubleshooting Error Mes-
sages in CX-Net Data Link Table Check .
Set the model of the PLC’s CPU Unit.
1 to 32
Set the address of the refresh nodes.
It cannot be set to a parameter exceeding the “maximum node
address” of the network parameter.
CIO Area: CIO 000 to CIO 6143
LR Area:
DM Area: DM 0000 to DM 32767
EM Area: Banks 00 to 15, EM 0000 to EM 32767
Unit Ver. 1.2 or later: The same memory areas can be set for
both Area 1 and Area 2.
*: When a word between LR 000 and LR 199 is specified, the
Remote nodes: 0 to the number of source words
Local node:
The total number of words in area 1 and area 2 in each node
must not exceed 4,000 for the CS1W-CLK23 or CJ1W-CLK23,
and must not exceed 1,000 for the CS1W-CLK21-V1 or CJ1W-
CLK21-V1.
The numbers of words in both area 1 and area 2 in each node
must not be set to 0.
Remote nodes: 0 to one less than number of source words
Local node:
This setting is not required if an offset is not used.
data link area will be allocated between CIO 1000 and
CIO 1199.
6143 (CIO Area)
199 (LR Area)
32767 (DM Area, EM Area)
L
(EM must be installed)
R 00 to LR 199 (*)
Set the number of words to be received.
0 to 4,000 (CS1W-CLK23, CJ1W-CLK23)
CS1W-CLK23, CJ1W-CLK23: 0 to 4,000
CS1W-CLK21-V1, CJ1W-CLK21-V1: 0 to 1,000
Set the number of words to be transmitted.
Set the offset for the data to be received.
Cannot be set.
Setting range
Setting range
Section 5-2
119

Related parts for CV500BI111