4-1
4-1-1
4-1-2
88
CS-series Controller Link Units
CS-series Controller Link Units
Overview
Unit Number
The following settings are required for a Controller Link Unit used with a CS-
series PLC.
Set the unit number for each Unit using the rotary switches on the front of the
Unit. The unit number is used to identify a CPU Bus Unit within the PLC. Any
unit number can be set between 0 and F in hexadecimal (00 to 15 in decimal)
Unit number
Node address
Baud rate
Terminating resistance
Item
Unit Number
Node Address
Baud Rate
Terminating Resistance
01 to F (default is 0)
01 to 32 (default is 01)
OFF
(factory default)
ON
OFF
ON
OFF
ON
Note: The factory default settings are shown above.
Front switch
Pin 1
Note Factory default setting is in bold.
Unit number setting switch
Node address switches
Baud rate, pins 1 and 2
Terminating resistance switch
Pins
Setting range
Setting range
OFF
OFF
ON
ON
Always leave pins 3 and 4 OFF.
Pin 2
Not connected
Connected
Terminating
resistance
2 Mbps
1 Mbps
500 Kbps
Cannot be set.
Baud rate
Switch
All nodes in the Network
All nodes in the Network
All nodes in the Network
Turn ON the terminating resis-
tance at the nodes at both
ends of the Network and turn it
OFF at all other nodes.
500 m
800 m
1 km
transmission
Maximum
distance
Nodes
Nodes
.
Nodes
Section 4-1
Set same
rate for all
nodes in the
Network.
88