8-1-3
Maximum Node Address
No. of Polled Nodes per
Communications Cycle
No. of Event-frames per
Communications Cycle
254
Communications Mechanism
Network Parameters
Note The default maximum node address will be set to 62 when the Wired Network
If the node is always to be connected as a polled node when the power is
turned on, set it as a polled node. If the node can become a polling node
when the power is turned on, set it as a polling node. One of the nodes set as
a polling node will serve as the actual polling node. Except for maintenance
after Unit replacement (see 9-6 Handling Precautions), set the Units all nodes
as polling nodes (set the polling node/polled node bit to “0”).
Network parameters are also used to control network operations. Network
parameters are read from the polling node and distributed to all other nodes
when the Controller Link Network is started. In this way, all nodes on the net-
work always have the same network parameter settings. If nodes are con-
nected to the network halfway during network operation, the network
parameter settings will also be distributed to these nodes when they are con-
nected. The following three network parameters can be specified.
This parameter specifies the maximum node address of nodes to be checked
by the polling node. The default is 32. (See note.) Reducing the setting of this
parameter reduces the number of nodes checked by the polling node and can
thus avoids unnecessary check operations. However, if the network contains
nodes with node addresses greater than the setting of the parameter, these
nodes will not be connected to the network.
62 Node Enable Bit in the DM Parameter Area software switches of the
CS1W-CLK21-V1, CS1W-CLK23, CJ1W-CLK21-V1, or CJ1W-CLK23 Unit is
ON and the Unit is restarted.
This parameter specifies the number of nodes to be checked (polled) by the
polling node during each polling cycle. The default is 4. Setting this parameter
to a high value increases the communications cycle time, but reduces the time
required to recognize that nodes have been removed from or added to the
network. Reducing the setting of this parameter shortens the communications
cycle time but delays a network response when a node is disconnected from
or connected to the network.
This parameter specifies the maximum number of event frames (communica-
tions other than data links, such as message service transmissions) that can
be transferred during a communications cycle. Specify a value in units of 128
bytes. The default is 35 (128 × 35 = 4,480 bytes).
Increasing the setting of this parameter increases the communications cycle
time but allows for more event communications such as the message service.
Too small a parameter value restricts event communications, resulting in an
error. See 8-2 Communications Cycle Time (on page 255) for the effects of
network parameters on communication cycle times.
Section 8-1