316
Error Log
0216
Hex
021A
Hex
021B
Hex
021C
Hex
0220
Hex
0221
Hex
0222
Hex
0223
Hex
0230
Hex
0300
Hex
0601
Hex
Error
code
Backup power supply error (Opti-
cal Units only)
Set table logic error
Hardware error
Data link error inactive
Reduced number of participating
nodes (separated nodes)
Data link stop requested
Packet discarded
Unit error
Contents
Note
1. Applicable PLCs: CV = CVM1 and CV-series PLCs, CS/CJ = CS-series
2. Errors indicated by error codes 0101 to 0116 are recorded only when the
3. Error code 0230 hex is only recorded for Controller Link Units with unit ver-
4. The data is written to EEPROM for the CS1W-CLK23 and CJ1W-CLK23.
and CJ-series PLCs, All = All models of PLC.
frame was discarded because transmission was impossible.
sion 1.2 or later.
00 Hex
00 Hex
00 Hex
Not set
Separated nodes 1 to 16
correspond to bits 0 to 15
(1st byte: bits 8 to 15, 2nd
byte: bits 0 to 7)
Separated nodes 17 to 32
correspond to bits 0 to 15
(1st byte: bits 8 to 15, 2nd
byte: bits 0 to 7)
Separated nodes 33 to 48
correspond to bits 0 to 15
(1st byte: bits 8 to 15, 2nd
byte: bits 0 to 7)
Separated nodes 49 to 62
correspond to bits 0 to 13
(1st byte: bits 8 to 15, 2nd
byte: bits 0 to 7)
Start node
address
Not set
Not set
1st byte
Detail code
Backup
power sup-
ply error dis-
tinction:
01 Hex:
OFF to ON
02 Hex: ON
to OFF
01 Hex: Net-
work param-
eters
02 Hex:
Data link
tables
03 Hex:
Routing
tables
Error status
(See note.)
Stop node
address
2nd byte
Check the status of
the backup power
supply and power
supply cables.
Remake and set the
appropriate data.
Check the unit ver-
sion.
Replace the Control-
ler Link Unit.
Restart the Control-
ler Link Unit.
Check the node
parameters, the sep-
arated nodes,
cables, and terminat-
ing resistance set-
tings.
Check the applica-
tion and Support
Software operation if
the data link was not
intentionally stopped.
Conduct an echo-
back test and find the
cause of the error.
Check the operating
environment.
Correction
No
Yes
No (See
note 4.)
Yes
No (See
note 4.)
Yes
No
Yes
Written to
EEPROM
Section 9-3
CS/CJ
All
All
All
CS/CJ
CS/CJ
All
All
Applicable
PLC