Introduction
RECV
@RECV(98)
S
D
C
C + 1 1
C + 2
C + 3
S: Destination node beginning send word
D: Source node beginning receive word
C: Source node first control data word
C
Note
1514
1514131211
0: Source network address not specified (local network)
1: Source network address specified.
15
Destination (transmission source) unit address
00 (Hex):
01 to 0F (Hex):
Destination network address
00 (Hex):
01 to 7F (Hex):
This setting is enabled only when "Destination network address specified" is set in word C.
When specifying the destination network address, set all the nodes in the routing tables. For
details on the routing tables, refer to
10 to 1F (Hex):
FE (Hex):
15
1
Always "1" for Controller Link Networks
Always "1" for Controller
Link Networks
0: Response required
1: Response not required
"m" number of send words
0000 to 03DE (Hex): 0 to 990 words
Number of retries
0 to F (Hex): 0 to 15 retries
Direct/Indirect
0: Direct; 1: Indirect
RECV receives “m” words beginning with S (the beginning word for data
transmission at the destination node, M) to the words from D (the beginning
word for data reception at the source node) onwards.
1. When communicating in the same network with CVM1 and CV-series
2. With the message service, there is no guarantee that a message to a des-
8 7
8 7
PLCs manufactured prior to April 1996, the local network address cannot
be set to “00.” Set a number other than “00” as the local network address
in the routing tables, and then specify that number.
tination node will reach its destination. It is always possible that the mes-
sage may be lost in transit due to noise or some other condition. When
0
PLC's CPU Unit
Computer (user program)
Local network
1 to 127
(02 to 0F (Hex) are used when
using Controller Link Support
Boards for PCI Bus only.)
Unit Nos. 0 to 15
Unit connected to network
0
0
0
0
0
Section 7 Network Interconnections.
Response monitor time
00 (Hex):
FF (Hex):
01 to FE (Hex):
D
m
15
Source node
Destination (transmission source) node address (M)
01 to 20 (Hex): 1 to 32 (or 01 to 3E (Hex): 1 to 62)
The range of node addresses will vary for networks
other than Controller Link Networks.
No response monitoring
0.1 to 25.4 s (unit: 0.1 s)
2 s (for 2 Mbps)
4 s (for 1 Mbps)
8 s (for 500 Kbps)
0
Destination node M
"m" num-
ber of
send
words
S
15
Section 6-1
0
179