CV500BI111 Omron, CV500BI111 Datasheet - Page 340

no-image

CV500BI111

Manufacturer Part Number
CV500BI111
Description
Programmable Logic Controller
Manufacturer
Omron
Datasheet

Specifications of CV500BI111

Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Error Log
0117
Hex
0118
Hex
0203
Hex
0206
Hex
0207
Hex
0208
Hex
0209
Hex
020C
Hex
0210
Hex
0211
Hex
0214
Hex
Error
code
Internal buffer full
Illegal packet discarded
EEPROM error
Number of participating nodes
decreased (local node still partic-
ipating)
Number of participating nodes
decreased (local node not partic-
ipating)
Polling node changed
Inconsistent network parameter
Time out with token
Communications controller send
error
Duplicate address error
Node address setting error
Contents
Command block
Bits 0 to 7:
Bits 8 to 14:
Bit 15:
Response block
Bits 0 to 7:
Bits 8 to 14:
Bit 15:
(1st byte: bits 8 to 15;
2nd byte, bits 0 to 7)
01 Hex:
Read error
02: Hex:
Write error
Network
parameters
maximum
node
address
Address of
previous
polling node
00 Hex
00 Hex
00 Hex
00 Hex
Not specified
Source node address
Source Network address
OFF
Destination node
address
Destination Network
address
ON
1st byte
Detail code
Address of
01 Hex:
Data link
tables
02 Hex:
Network
parameters
03 Hex:
Routing
tables
Number of
non-partici-
pating nodes
Address of
new polling
node
polling node
Error status
(See note.)
Error status
(See note.)
Local node
address
2nd byte
Increase number of
retries or reconfig-
ure system to distrib-
ute load.
Check for nodes
sending illegal
packets.
For CVM1 and CV-
series PLCs, check
that the PLC is not
protected.
Remake and set the
relevant data. If the
error occurs again for
the CVM1 and
CV-series, replace
the CPU Unit and for
the C200HX/HG/HE
PLCs, replace the
Controller Link Unit.
Check network
parameters, node
participation, cables,
and terminating
resistance.
Check previous
polling node.
Using the Controller
Link Support Soft-
ware, check network
parameters.
Check network
parameters, node
participation, cables,
and terminating
resistance.
Replace the Control-
ler Link Unit.
Reset so that each
node address is used
only once within the
same Network.
Check the node
address settings and
correct them.
Correction
No
Yes
Yes
No (See
note 4.)
No (See
note 4.)
No (See
note 4.)
Yes
No
Yes
No (See
note 4.)
Yes
Written to
EEPROM
Section 9-3
All
All
C200HX/HG/
HE, CV,
CQM1H
All
All
All
All
All
All
All
CS/CJ,
CQM1H
Applicable
PLC
315