148
Setting Data Links
Send size (number of
words) for node of area 1
Area 2 data link start
word
Area 2 type
Send size (number of
words) for node of area 2
First data link status word Set in BCD the first word used for storing data link status.
Nodes to participate in
the data links
Note a) The total number of words in data link send and receive areas
Item
b) The following values must be satisfied for each node for the data
c) When using area 1 only, set the data link start word, type, and
d) When using area 2 only, set the data link start word, type, and
e) The startup node must be set as a participating node of the data
must not exceed 8,000 per node.
link area 1 and area 2 so that the final word in the data link does
not go beyond the last word in the PLC memory area.
(Data link start word – 1) + Total number of send/receive
words in area
the number of send words of area 2 to 0.
the number of send words of area 1 to 0.
links. If not, the data links will not start.
Set the number of words in BCD between 0 and 1,000.
The total number of send words for area 1 and area 2
must not exceed 1,000.
When area 1 is not used, set to 0.
Set the word address in BCD.
DM Area: DM 0000 to DM 5999
EM Area: Banks 00 to 15, EM 0000 to EM 6143
Set the area type for area 2 in BCD.
DM Area: 82
EM Area: Banks 00 to 07: 90 to 97
Area 2 not used: 00
Set the number of words in BCD between 0 and 1,000.
The total number of send words of area 1 and area 2
must not exceed 1,000.
When area 2 is not used, set to 0.
An area of 16 words is used for storing status.
0 (*), IR 001 to IR 220, IR 300 to IR 496
Status is stored in the IR or CIO Area only.
*: When 0 is set, status of nodes 1 to 6 is stored in
Set to ON (1) the bits corresponding to the nodes partici-
pating in the data links.
The data link will not start unless the startup node itself is
set as a participating node.
The data link will not start if the node is set to a parameter
exceeding the “maximum node address” of the network
parameter.
CIO 239 to CIO 241 for level 0 and in CIO 243 to CIO
245 for level 1.
235 (First word IR 000 to IR 235)
511 (First word IR 300 to IR 511)
63 (LR Area)
5999 (DM Area)
6143 (EM Area)
Banks 08 to 15: A8 to AF
Setting range
Section 5-2