CV500BI111 Omron, CV500BI111 Datasheet - Page 202

no-image

CV500BI111

Manufacturer Part Number
CV500BI111
Description
Programmable Logic Controller
Manufacturer
Omron
Datasheet

Specifications of CV500BI111

Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Introduction
RECV
(↑)RECV(193)
D
C
S
C+1
C+2
S: Source node beginning send word
D: Destination node beginning receive word
C: Source node first control data word
C
15
15
15
Destination node M
01 to 20 (Hex): 1 to 32 (or 01 to 3E (Hex): 1 to 62)
The range of node addresses will vary for networks
other than Controller Link Networks.
0
Note
"m" number of send words
0001 to 03DE (Hex): 1 to 990 words
11
11
0
8 7
8 7
Destination network address
00 (Hex): Local network
01 to 7F (Hex): 1 to 127
RECV receives “m” words beginning with S (the beginning word for data
transmission at the destination node, M) to the words beginning with D (the
beginning word for data reception at the source node).
1. When using CVM1 and CV-series PLCs manufactured prior to April 1996,
2. With the message service, there is no guarantee that a message to a des-
Destination unit address
00 (Hex):
01 to 0F (Hex): Computer (user program)
10 to 1F (Hex): Unit nos. 0 to 15
FE (Hex):
the local network address cannot be set to “00.” Set a number other than
“00” as the local network address in the routing tables, and then specify
that number.
tination node will reach its destination. It is always possible that the mes-
sage may be lost in transit due to noise or some other condition. When
using the message service, it is advisable to prevent this situation from oc-
curring by performing resend processing at the node where instructions
are issued. With the SEND, RECV, and CMND instructions, resend pro-
cessing is performed automatically once the number of retries has been
set, so be sure to specify a number other than “0” for the number of retries.
0
0
0
PLC's CPU Unit
Unit connected to network
(02 to 0F (Hex) are used
when using Controller Link
Support Boards for PCI Bus
only.)
D
m
C+3
C+4
15
Source node
15
0: Response required
1: Response not required
0
10 8 7
0
Communication port No.
0 to 7
Response monitor time
0000 (Hex): 2 s
0001 to FFFF (Hex): 0.1 to 6,553.5 s
(Unit: 0.1 s)
If the baud rate is slow, then setting a small
value may generate an error. The standard is
approximately 4 seconds at 1 Mbps or 8
seconds at 500 Kbps.
0
3
"m" num-
ber of
send
words
Destination node M
Number of retries
0
0 to F (Hex): 0 to 15 retries
S
15
Section 6-1
0
177